/ EN_TPS-60-PRO_05 / 25. 03. 2020
- 13 -
3.3 Terminal assignment terminal block X1
Sliding gate operator TPS 60 PRO
If no ST
OP
button
is con
-
nected, bridge the termi
-
nals 31/37 (jumper as factory settings).
Terminal block X1
TPS 60 PRO
Function main closing edge
(ME):
safety
when closing
Function side closing edge
(SE):
safety
when opening
ME
SE
CLOSE
OPEN
Only by means
of I-loop detec-
tor active
EMERGENCY
:
If necessary
, the emergency stop
switch terminal S1/S1 switches the
motor off through the contactor
.
pre-wired
8,2kOhm
8,2kOhm
31
37
30
32
30
33
30
34
35
36
58
59
40
41
40
43
46
47
50
51
50
52
9/1
9/2
9/3
9/4
70
71
+
–
90
91
92
93
60
61
60
63
S1
S1
10
1
1
L1
L2
L3
N
grounding
power supply 380V a.c.
Photocell 230V a.c., max. 100W
emergency switch (spring rod switch)
grounding
limit switch LEFT
limit switch RIGHT
potential-free signal contact 2
contact load 24Vd.c., 1A
potential-free signal contact1
contact load 24Vd.c., 1A
control lamp, 24V, max. 2W
induction loop 2
induction loop 1
main safety edge
(ME)
side safety edge
(SE)
photocell-contact
supply photocell-receiver
supply photocell-transmitter
emergency release
IMPULSE - button (decoupled) (see page 25)
pedestrian switch
CLOSE - button
IMPULSE - button
STOP - button
The stop input has no emergency stop function! - In order to ensure the emergency stop function, provide
the supply line with an all-pole disconnecting emergency stop switch, that locks after actuation!