5056.4252155D
Figure 13: Non-combustible board
location.
NON-COMBUSTIBLE
BOARD
If fi nishing the wall above the unit with
paint, the framing kit shipped with the
unit should be discarded.Use full sheets
of calcium silicate board or equivalent
and full length metal studs to fi nish and
frame around the unit.
Calcium silicate board is a high grade
material with cement, quartz and natural
minerals as the main raw materials.
(Note: Calcium Silicate is 1/2” thick)
CAUTION: Calcium Silicate board
can be damaged if dropped or struck.
Handle with care. Inspect board prior to
installation and do not use if cracked.
NOTE: It is recommended to pre-drill
mounting holes in the board prior to
securing to the framing. This will pre-
vent the board from cracking.
12”
9 5/8”
12”
Figure 11: Non-combustible board within frame.
NON-COMBUSTIBLE RECESSED
INSTALLATION DETAIL
This fi replace may be recessed up
to a maximum depth of 4 1/2”. This
recess must be constructed from
non- combustible material.
Finishing material must not pro-
trude past framing fl anges under
ANY circumstance. The safety
screen and the window, with trim
fi tted, must be able to move freely.
Figure 12: TCWS54D Reccessed installation details.
31 1/2"
44 9/16"
74 13/16"
81 11/16"
81 11/16"
115 9/16"
55 1/4"
74 13/16"
NOTE: FIREPLACE SHOULD BE IN ITS FINAL LOCATION BEFORE FRAMING
RANGE
23 11/16"
to
25 7/16"
RANGE
25 3/8”
to
26 7/8"
RANGE
1/32"
to
3 3/16"
11 3/4"
FRAMING
LINTEL
74 3/4"
Figure 14: TCWS54D Minimum combustible framing.
Non - combustible board area
TCWS54D Minimum Combustible Framing Dimensions
NON-COMBUSTIBLE
MATERIAL MUST EXTEND
12" ABOVE, 9 5/8" TO
THE SIDES AND 12”
BELOW THE FRAMING
EDGES.
NON-COMBUSTIBLE
BOARD
10
TCWS54_D 150817-40