12
1. Set temperature:18-30
℃
℃
℃
℃
2. Compressor and indoor fan action:
Ts = set temperature Ta= room temperature T=Ta -Ts
T Compressor
Indoor
fan
T
≥
1
℃
On
High flow middle flow Low flow
T
≤
-1
℃
Off
High flow Low flow
3. Indoor fan action
3.1 Fan speed in cooling mode
:
:
:
:
1) High Flow Selected
—
Strong Wind sent out
2) Middle Flow Selected
—
Middle Wind sent out
3) Low Flow Selected
—
Breeze Wind sent out
3.2 Fan speed in auto mode:
1) Ta – Ts
≥
4
℃
, It will be in high Flow.
2) Ta – Ts
≤
0
℃
, It will be in low Flow.
3) Ta – Ts
=
2
℃
, It will be in middle Flow.
3.3 When 9
℃≤
℃≤
℃≤
℃≤
Ta – Ts
≤
≤
≤
≤
4
℃
℃
℃
℃
, indoor fan works as following chart:
High wind
Middle wind
Low wind
0 2 4 Ta – Ts (
℃
℃
℃
℃
)
4. Indoor fan motor speed:
Strong: 1320 r/min High: 1260 r/min Middle: 1150 r/min
Low: 960 r/min Breeze: 600 r/min Economic: 840 r/min
Remarks: Different models maybe be different about fan motor speed. The speed is
for reference only.
5. Continued working function in Cooling Mode:
When Ts is less than 18
℃
or more than 30
℃
, “CONT” is shown on remote control, and the air conditioner works in
continued working mode.
1) Compressor works in cooling mode automatically.
2) When “AUTO” fan speed is selected, indoor fan speed works in middle flow mode.
3) Air flow direction can be adjusted by remote control in natural flow, swing or fix mode.