101
19. Press the [SET] key.
・
The change is confirmed, and "S-05" is displayed again.
・
The display of the setting value automatically returns to that
of the setting item in ten seconds. Unless the [SET] key is
pressed while a setting value is displayed, it is not confirmed.
20. Turn off the converter, and open the front cover.
21. Remove the short-circuit wire between the terminals [AIN2]
and [G-IN] on <IO66-Z>.
22. Connect a voltage generator to the terminals [AIN2] and
[G-IN].
・
Keep the terminals [G] and [G-IN] on <IO66-Z> short-circuited.
23. Install a DC voltage meter or tester between the terminals
[AIN2] and [GND].
24. Close the front cover and turn on the converter.
25. Press the [MONI/FNC] key.
・
The [FNC] LED turns on, and the first setting item of the basic setting area is displayed.
26. Press the keys [
↑
] or [
↓
] to display "S-00."
27. Press the [
→
] key to blink numbers, and then press the keys
[
↑
] or [
↓
] to change them to "S-05."
28. Press the [SET] key.
・
"0" is displayed on the extreme right, and the underscore blinks
on the extreme left.
29. Press the [
→
] key to blink required digits, and then press
the keys [
↑
] or [
↓
] to specify "1040."
Voltage generator