42
4.2.4.
Checking Operating State
The converter can display data such as AC frequency, current, and voltage on the console while it is running.
A total of 25 monitor items are provided. For contents of each item, refer to {4.1.5. List of Monitor Items}.
To change a monitor item, perform the following steps on the console:
1. When the [FNC] LED on the console is on, press the [MONI/FNC] key.
・
The [FNC] LED turns off, and the console enters the monitor (MONI) mode.
2. The monitor item currently set is displayed.
"Vdc" shows a DC voltage.
・
About one second later, data of the monitor item is
automatically displayed.
DC voltage shows 340.0 V.
3. Press either of the [SET] key, [
↑
] key, or [
↓
] key to return
to the display of the monitor item.
Example showing a DC voltage: Vdc
4. Press either of the [SET] key, [
↑
] key, or [
↓
] key while the monitor item is displayed.
・
The next monitor item is displayed.
・
About one second later, data of the monitor item is
automatically displayed.
・
The display order of the monitor items will differ between the
[SET]/[
↑
] key and the [
↓
] key.
Display after pressing the [
↑
] key
[SET] key, [
↑
] key
Top to bottom in the list
of monitor items
[
↓
] key
Bottom to top in the list
of monitor items
For the types and order of monitor items, refer to the next section {4.1.5. List of Monitor Items}.