48
4.4.
Start and Stop through External Contact
You can start and stop the converter by installing an external contact, in addition to using the [START] key
and the [STOP/RESET] key on the console.
Connect the external contact to the control input terminal [START] of the terminal block TB1 on the control
board <VFC66R-Z>.
This section provides a configuration and operating procedures for installing the external contact to start
and stop the converter.
■
Checking jumper socket position
Check the position of the jumper socket for a jumper pin next to the terminal block TB1 on the control board
<VFC66R-Z>.
・
When it is positioned at [CN-SO], this indicates PS common input (source input).
・
When it is positioned at [CN-SI], this indicates GND common input (sink input).
1. Turn off the converter.
2. Open the front cover.
・
For how to open the front cover, refer to {3.2. How to Open and Close Front Cover}.
・
Use the Phillips screwdriver (M4).
3. Check the position of the jumper socket for a jumper pin.
4. Close the front cover.
Control board VFC66R-Z
Terminal
block
TB1
Console board SET66-Z
Jumper pin