49
■
Installing the external contact and changing settings
This section provides procedures for installation and settings when the jumper socket is positioned at [CN-SO]
(PS common input).
When it is positioned at [CN-SI] (GND common input), you should replace a terminal [PS] with a terminal [GND]
in the procedures.
The parameter to be changed is the operation command source selection: <b-03>.
For details of how to change parameter settings, refer to {4.2.3. Changing Parameter Settings}.
Warning
Installation of the external contact
●
Be sure to turn off the converter before installing the external contact.
Otherwise, it can result in a risk of electric shock.
●
Be sure to turn off the external contact to be installed.
If it is installed with it turned on, a high voltage may be output when the converter is turned on.
Prepared items
・
Phillips screwdriver (M3)
・
Phillips screwdriver (M4)
・
External contact
1. Turn off the converter.
2. Open the front cover.
・
For how to open the front cover, refer to {3.2. How to Open and Close Front Cover}.
・
Use the Phillips screwdriver (M4).
3. Install the external contact between the control input terminal [START] and the terminal [PS] of the terminal
block on the control board <VFC66R-Z>.
・
For the terminal block and the position of terminals, refer to
{3.3.1. How to Connect Converter Terminals}.
・
Use the Phillips screwdriver (M3).
4. Close the front cover and turn on the converter.
5. When the [FNC] LED on the console is off, press the [MONI/FNC] key.
・
The [FNC] LED turns on, and a setting item appears in the seven-segment display. For example, immediately
after the converter is turned on, the first item of the basic setting area is displayed.
External contact