63
5.3.4.
Area c (multifunction input/output related setting area)
In the area c, set the parameters related to the multifunction input/output on the terminal block of the converter.
■
c-00 through c-06
Multifunction input
Display Contents
Setting range (Selecting item)
Initialized
data
Unit
Write
during
operation
c-00
Multifunction input
source selection
0: Terminal block
1: Digital communication option
0
-
x
c-01
Multifunction input
terminal (6)
[MI6] function selection
0: External failure signal 1
(Protection relay 86A active)
1: External failure signal 2
(Protection relay 86A active)
2: External failure signal 3
(Protection relay 86A active)
3: External failure signal 4
(Protection relay 86A active)
4: External failure signal 1
(Protection relay 86A inactive)
5: External failure signal 2
(Protection relay 86A inactive)
6: External failure signal 3
(Protection relay 86A inactive)
7: External failure signal 4
(Protection relay 86A inactive)
8: Traceback external trigger
9: Emergency stop (B contact)
0
-
x
c-02
Multifunction input
terminal (7)
[MI7] function selection
1
-
x
c-03
Multifunction input
terminal (8)
[MI8] function selection
2
-
x
c-04
Multifunction input
terminal (9)
[MI9] function selection
3
-
x
c-05
Multifunction input
terminal (10)
[MI10] function selection
3
-
x
c-06
Multifunction input
terminal (11)
[MI11] function selection
3
-
x
Install and set the digital communication option to use the function of multifunction input terminal.
For how to set the digital communication option, refer to {5.3.11. Area J}.
Multifunction input source selection: c-00
With the multifunction input source: c-00 set to "1" (Digital communication option), the multifunction input
is controlled by digital communication.
Multifunction input terminal (6) [MI6] through (11) [MI11] function selection: c-01 through c-06
In these parameters, set the function allocated to the multifunction input terminal (6) [MI6] through (11) [MI11].