68
5.3.5.
Area d (converter operation setting area)
In the area d, set the converter operation parameters.
■
d-00 through d-08
DC voltage command related settings
Display Contents
Setting range (Selecting item)
initialized
data
Unit
Write
during
operation
d-00
DC voltage command
fixed mode selection
0: OFF (DC voltage command variation
mode)
1: ON (DC voltage command fixed mode)
0: OFF
-
x
d-01
DC voltage command
gain
1.56 to 1.90
1.58
-
x
d-02
DC voltage command
upper limit
300.0 to 358.0 (200 V class)
600.0 to 716.0 (400 V class)
358.0 (200 V)
716.0 (400 V)
V
x
d-03
DC voltage command
lower limit
300.0 (200 V)
600.0 (400 V)
V
x
d-04
Soft start time
0.0 to 600.0
1.0
sec
x
d-05
through
08
For special
adjustment
*
-
x
DC voltage command fixed mode selection: d-00
Select whether to use the fixed mode for the DC voltage command.
OFF: The DC voltage command variation mode is entered, and the DC voltage command varies with the AC voltage.
In this case, the DC voltage command is determined as follows:
DC voltage command = Effective value of AC line voltage x DC
voltage command gain: d-01
ON: The DC voltage command fixed mode is entered, and the DC voltage command is fixed to the setting of the
basic setting item "0.VrEF."
(Refer to the description of basic setting item 0.VrEF in this manual.)
DC voltage command gain: d-01
When the DC voltage command fixed mode selection: d-00 is set to OFF, the DC voltage command becomes a value
obtained by "effective value of AC line voltage x d-01."
DC voltage command upper limit: d-02
Set the upper limit of DC voltage command for the case that the DC voltage command fixed mode selection: d-00
is set to OFF.
DC voltage command lower limit: d-03
Set the lower limit of DC voltage command for the case that the DC voltage command fixed mode selection: d-00
is set to OFF.
* Caution
A DC voltage command cannot be set lower than a value obtained by "effective value of AC line voltage x 1.56
(V)."