69
When a value obtained by "effective value of AC line voltage x 1.56 (V)" becomes higher than the setting of
d-02 (DC voltage command upper limit), a DC voltage command becomes a value obtained by "effective value of
AC line voltage x 1.56 (V)."
Note that the maximum DC voltage command is 358 V (200 V class)/716 V (400 V class).
When the DC voltage command source selection: b-03 is set to a value other than "0," the DC voltage command
from the specified place takes priority.
For d-02 and d-03, setting with the console can be done in increments of 0.1 V for the 400 V class unit. However,
the setting is reflected in increments of 0.2 V internally. Keep this in mind.