These are DC voltage control gains. To keep both the stable characteristic in a steady state and response
characteristic in a transient state, the variable proportional gain PI controller is adopted. E-03 through E-06
are used to configure the settings related to variable proportional gain, and E-07 is used to set an integral
gain.
Normally, do not change the initial values.
Adjust variable structure proportional gain which changes proportional gain depending on the difference between
a DC voltage command and DC voltage.
* Caution
For E-06, setting with the console
can be done in increments of 0.1 V for
the 400 V class unit. However, the
setting is reflected in increments
of 0.2 V internally. Keep this in
mind.
直流電圧偏差
(
絶対値
)
<
E-06
>
<
E-03
>
比例ゲイン
最大比例ゲイン
基本比例ゲイン
<
E-04
>
可変開始電圧
<
E-05
>
可変傾斜率
可変構造比例ゲイン
Proportional gain
Maximum proportional gain
Basic proportional gain
Variable structure proportional gain
Variable ramp rate
Variable start voltage
DC voltage deviation (absolute value)