76
Traceback pitch: F-08
Set an interval of traceback.
Traceback trigger point: F-09
Set a traceback trigger point.
Traceback CH1 through CH12 selection: F-10 through F-21
Select whether to use the converter internal data for
each channel of traceback.
* Caution
The traceback pitch and traceback point should be set before traceback data of protection operations and ot
hers is captured.
F-10 through 21
settings
0
1 to 12
Recorded data
Dimension
Recorded data
ch1
U phase current
2357digit
= Unit rated AC current
PLC output RAM (1 through 12)
(Settings of F-10 through 21
become the selection of output
RAM.)
ch2
V phase current
ch3
W phase current
ch4
DC voltage
10digit/V(200V)
5digit/V(400V)
ch5
U phase
power supply
voltage
ch6
V phase
power supply
voltage
ch7
W phase
power supply
voltage
ch8
U phase control voltage
ch9
V phase control voltage
ch10
W phase control voltage
ch11
DC voltage command
10 digit/V (200/400 V)
ch12
Active current command
9700digit
= Unit rated AC current
Traceback
data
<
F-09
>
Trigger point
0
100
Traceback point setting