78
■
J-01 through J-08
Digital communication option settings
Display Contents
Setting range (Selecting item)
initialized
data
Unit
Write
during
operation
J-01
<ASYC66-Z>
<CC66-Z>
Option baud rate
Using <ASYC66-Z>
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps 5: 38400 bps
Using <CC66-Z>
0: 156 kbps
1: 625 kbps
2: 2.5 Mbps
3: 5 Mbps
4: 10 Mbps
5: 10 Mbps
4
-
○
J-02
<OPCN66-Z>
Option baud rate
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: 1 Mbps
4: (For special adjustment)
*
3
-
x
J-03
<OPCN66-Z>
Number of option
input frames
(-> master)
3 to 19
14
-
x
J-04
<OPCN66-Z>
Number of option
output frames
(master ->)
2 to 12
6
-
x
J-05
<ASYC66-Z>
<OPCN66-Z>
Transmission wait time
selection
<CC66-Z>
CC-Link version number of
occupied stations selection
Using <ASYC66-Z>
0: 0 ms
1: 5 ms
2: 10 ms
3: 20 ms
4: 40 ms
5: 60 ms
6: 100 ms
Using <OPCN66-Z>
Baud rate (J-02)
(125 k/250 k/200 k/1 Mbps)
0: 200/200/200/200
μ
s
1: 200/200/200/200
μ
s
2: 200/200/200/200
μ
s
3: 200/200/200/200
μ
s
4: 200/150/150/150
μ
s
5: 200/100/100/100
μ
s
6: 200/100/50/50
μ
s
Using <CC66-Z>
Version/number of occupied stations
0: 1.1/1
1: 1.1/2
2: 1.1/3
3: 1.1/4
4: 2.0 (double)/1 5: 2.0 (4 times)/1
6: 2.0 (8 times)/1
0
-
x
J-06
<ASYC66-Z>
Communication mode selection
0: Standard communication mode
0
-
x
J-07
Date/Time data selection
from communication
0: Without date/time data
1: With date/time data
0
-
x
For details, refer to the manuals of digital communication options.