79
5.3.10.
Area L (analog input/output setting area)
In the area L, you can set parameters such as analog input/output gain and offset of the converter.
■
L-00
Display Contents
Setting range (Selecting item)
Initialized
data
Unit
Write
during
operation
L-00
Vdc_detection_gain
80.0 to 120.0
100.0
%
x
DC voltage detection gain: L-00
This parameter indicates detection adjustment gain of DC voltage detected by the converter.
By inputting the voltage between the DC terminals [+] and [-] during converter initialization, this DC voltage
detection gain is back calculated and the resulted value is set to this parameter. Normally, use it without
changing the initialized value.
When the gate board <GAC66>, etc. is replaced, an error may occur between "Vdc" display on the console and the
actual voltage between the DC terminals [+] and [-]. In this case, to adjust DC voltage detection gain without
initializing memory, refer to {5.4.3. DC Voltage Detection Gain Adjustment}.
Also, when the control board <VFC66R-Z> is replaced, refer to {5.4.3. DC Voltage Detection Gain Adjustment}
and perform adjustment.
■
L-01 and L-02
Analog output selection
Display Contents
Setting range (Selecting item)
Initialized
data
Unit
Write
during
operation
L-01
Analog output (2)
selection
0: AC voltage
1: AC current
2: AC frequency
3: AC power
4: DC voltage
5: Internal PLC output
6: Calibration
7: (For special adjustment)
*
8: (For special adjustment)
*
1
-
x
L-02
Analog output (3)
selection
0
-
x
*: Do not set this item.
Analog output selection: L-01 and L-02
With these parameters, select the analog output between the analog output (2) terminal [AOT2]/analog output
(3) terminal [AOT3] and the terminal [G-OT]. Install an optional board to use the analog output.
Analog outputs selected by L-01 and L-02
Selection items
Output voltage
Selection items
Output voltage
0
AC voltage
7.5/200 V (200 V class)
7.5/400 V (400 V class)
4
DC voltage
7.5/300 V (200 V class)
7.5/600 V (400 V class)
1
AC current
5 V/rated converter current
(Indicates an effective
value)
5
Built-in PLC output 5 V/20000 (100 %)
2
AC frequency
5 V/50 Hz
6
Calibration
Output 5 V
3
AC power
5 V/rated power
*
*: The rated power is obtained by
√
3 x voltage x rated unit current.