93
■
Comparing data between the converter main unit and <SET66R-Z>
To compare setting data between the converter main unit and <SET66R-Z>, perform the following steps:
This function is useful when setting data of <SET66R-Z> shall be original data of multiple converters.
Use "104" of the Special mode selection <S-00>.
For details of the special mode selection: S-00, refer to {5.3.14. Area S}. For details of how to change parameter
settings, refer to {4.2.3. Changing Parameter Settings}.
When the external console option is connected
●
When <SET66R-Z> has been connected to the converter main unit, the console on the main unit cannot be used.
Also, when the main unit cannot communicate with <SET66R-Z>, <SET66R-Z> does not react. Check connections between them
and others.
1. Connect the console of
the converter main unit to
<SET66R-Z>.
VF66R
・ ・ ・
・・・
・ ・ ・
・・・
・ ・ ・
・・・
Converter
External console option
SET66R-Z
Console
2. When the [FNC] LED on the console is off, press the [MONI/FNC] key.
・
The [FNC] LED turns on, and a setting item appears in the seven-segment display. For example, immediately
after the converter is turned on, the first item of the basic setting area is displayed.
3. Press the keys [
↑
] or [
↓
] to display "S-00."
4. Press the [SET] key.
・
"0" is displayed on the extreme right, and the underscore blinks
on the extreme left.
5. Press the [
→
] key to blink required digits, and then press
the keys [
↑
] or [
↓
] to specify numbers to become "1040."
6. Press the [SET] key.
・
The password input is confirmed, and the screen returns to
"S-00" display.
・
When a different number from "1040" is input, "P-Err" indicating
an error is displayed. In this case, press the keys [
↑
] or [
↓
]
to return to "S-00." Follow the procedures again from the step
4.
Display indicating a password error