94
7. Press the [SET] key.
・
Again, "0" is displayed on the extreme right, and the underscore
blinks on the extreme left.
8. Press the [
→
] key to blink a required digit, and then press the keys [
↑
] or [
↓
] to change the number
to "104."
・
The display of the setting value automatically returns to that
of the setting item in ten seconds. Unless a setting value is
specified while it is displayed, it cannot be changed.
9. Press the [SET] key.
・
The display of the setting value automatically returns to that
of the setting item in ten seconds. Unless the [SET] key is
pressed while a setting value is displayed, it is not confirmed.
・
The change is confirmed, and "ConP" and "SurE" blink
alternately.
↓↑
10. Press the [SET] key.
・
The setting is confirmed, and "ConP" is displayed.
Data is being compared
・
Compare data of the converter main unit with that of <SET66R-Z>.
When they match, "End" is displayed.
・
Setting data does not match:
Any of "CErr1," "CErr2" and "CErrA" blinks.
・
When communication between the main unit and <SET66EX-Z> is
disconnected during transfer, transfer is interrupted.
(1) Interrupted with the setting block displayed
(2) Interrupted ten seconds after blinking "rErr"
In either case, the setting block is displayed after
interruption and then the monitor item display returns. Perform
again the procedures from the first step.
Communication error indication
・
In a few seconds, the setting block is displayed, and then a
monitor item is displayed.