6. Press the keys [
↑
] or [
↓
] to display "S-00."
7. Press the [
→
] key to blink numbers, and then press the keys
[
↑
] or [
↓
] to change them to become "S-03."
8. Press the [SET] key.
・
"0" is displayed on the extreme right, and the underscore blinks
on the extreme left.
9. Press the [
→
] key to blink required digits, and then press
the keys [
↑
] or [
↓
] to specify numbers to become "1040."
10. Press the [SET] key.
・
The password input is confirmed, and the screen returns to
"S-03" display.
・
When a different number from "1040" is input, "P-Err" indicating
an error is displayed. In this case, press the keys [
↑
] or [
↓
]
to return to "S-03."
Follow the procedures again from the step 8.
Display indicating a password error
11. Press the [SET] key.
・
"0" is displayed on the extreme right, and the underscore blinks
on the extreme left.
12. Press the [
→
] key to blink required digits, and then press the keys [
↑
] or [
↓
] to change numbers to
a value measured by the voltage meter or the tester.
・
The display of the setting value automatically returns to that
of the setting item in ten seconds. Unless a setting value is
specified while it is displayed, it cannot be changed.
Specify "339.6" if the measured value is
339.6V
13. Press the [SET] key.
・
The display of the setting value automatically returns to that
of the setting item in ten seconds. Unless the [SET] key is
pressed while a setting value is displayed, it is not confirmed.
・
The setting of the DC voltage detection gain: L-00 is
automatically changed, and then "S-03" is displayed again.