The Specification of Power
42
Ceiling & Floor Type
8. The Specification of Power
Model(Btu/h) 48000
60000
48000-60000
INDOOR UNIT
POWER
Phase
1-phase 1-phase 1-phase
Frequency and
Voltage
220-240V, 50Hz
220-240V, 50Hz 220-240V, 50Hz
Power Wiring
(mm
2
)
3×1.0 3×1.0 3×1.0
Circuit Breaker/Fuse
(A)
15/10 15/10 15/10
OUTDOOR UNIT
POWER
Phase
3-phase
Frequency and
Voltage
380-415V, 50Hz
Power Wiring
(mm
2
)
5×2.5
Circuit Breaker/Fuse
(A)
50/40
Indoor/Outdoor Connecting Wiring
(Weak Electric Signal) (mm
2
)
3×0.5
Indoor/Outdoor Connecting Wiring
(Strong Electric Signal) (mm
2
)
Summary of Contents for CCT 140IUINV
Page 13: ...Service Space Super Slim Cassette Type 13 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 14: ...Wiring Diagrams 14 Super Slim Cassette Type 4 Wiring Diagram CCT140 IUINV CCT160 IUINV ...
Page 26: ...Wiring Diagrams Duct Type 27 4 Wiring Diagrams DCT140 IUINV DCT160 IUINV ...
Page 32: ...Field Wiring Duct Type 33 10 Field Wiring ...
Page 35: ...Service Space Ceiling Floor Type 37 3 Service Space ...
Page 36: ...Wiring Diagrams 38 Ceiling Floor Type 4 Wiring Diagrams CFT140 IUINV CFT160 IUINV ...
Page 41: ...Field Wiring Ceiling Floor Type 43 9 Field Wiring ...
Page 45: ...Service Space GA Floor standing Type 47 3 Service Space ...
Page 46: ...Wiring Diagrams 48 GA Floor standing Type 4 Wiring Diagrams FS140IUINV FS160IUINV ...
Page 56: ...Wiring Diagrams 70 Outdoor Units OU 1403 IUINV OU 1603 IUINV ...
Page 80: ...Troubleshooting Electrical Control System 121 2 4 2 3 Up down panel is not closed ...
Page 88: ...Troubleshooting Electrical Control System 129 2 4 3 8 P0 malfunction ...
Page 89: ...Troubleshooting 130 Electrical Control System 2 4 3 9 P1 malfunction ...
Page 90: ...Troubleshooting Electrical Control System 131 2 4 3 10 P2 malfunction ...
Page 91: ...Troubleshooting 132 Electrical Control System 2 4 3 11 P3 malfunction ...