Electrical Control Function
102
Electrical Control System
1. Electrical Control Function
1.1 Definition
T1: Indoor room temperature
T2: Coil temperature of indoor heat exchanger middle.
T2B: Coil temperature of indoor heat exchanger outlet.
T3: Coil temperature of condenser
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
1.2 Main Protection
1.2.1 Time delay at restart for compressor.
1.2.2 Temperature protection of compressor top
The unit will stop working when the compressor top temp. protector cut off, and will restart after the
compressor top temp. protector restart.
1.2.3 Temperature protection of compressor discharge
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules:
----If 102
℃
<T5<115
℃
, decrease the frequency to the lower level every 2 minutes till to F1.
---If T5>115
℃
for 10 seconds, the compressor will stop and restart till T5<90
℃
.
1.2.4 Sensor protection at open circuit and breaking disconnection.
1.2.5 Indoor fan delayed open function
For floor-standing:
When the unit starts up, the louver will be active immediately and the indoor fan will open 5s later.
If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind function.
For other models:
When the unit starts up, the louver will be active immediately and the indoor fan will open 10s later.
If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind function.
1.2.6 Fan speed is out of control
For A5 duct &Ceiling&floor:When indoor fan speed keeps too low (lower than 300RPM) for 50s, the indoor
fan will shut off and restart 30s later, if protection happened 3 times when fan motor restart continuously, the
unit will stop and the LED will display the failure.
For super slim cassette: When indoor fan speed keeps too low (lower than 200RPM) for 50s, the unit will
stop and the LED will display the failure.
For GA floor-standing: When indoor fan speed keeps too low (lower than 300RPM) for 50s, the unit will stop
and the LED will display the failure.
For M floor-standing: When indoor fan speed keeps too low (lower than 300RPM) for 10s, the unit will stop
and the LED will display the failure.
Summary of Contents for CCT 140IUINV
Page 13: ...Service Space Super Slim Cassette Type 13 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 14: ...Wiring Diagrams 14 Super Slim Cassette Type 4 Wiring Diagram CCT140 IUINV CCT160 IUINV ...
Page 26: ...Wiring Diagrams Duct Type 27 4 Wiring Diagrams DCT140 IUINV DCT160 IUINV ...
Page 32: ...Field Wiring Duct Type 33 10 Field Wiring ...
Page 35: ...Service Space Ceiling Floor Type 37 3 Service Space ...
Page 36: ...Wiring Diagrams 38 Ceiling Floor Type 4 Wiring Diagrams CFT140 IUINV CFT160 IUINV ...
Page 41: ...Field Wiring Ceiling Floor Type 43 9 Field Wiring ...
Page 45: ...Service Space GA Floor standing Type 47 3 Service Space ...
Page 46: ...Wiring Diagrams 48 GA Floor standing Type 4 Wiring Diagrams FS140IUINV FS160IUINV ...
Page 56: ...Wiring Diagrams 70 Outdoor Units OU 1403 IUINV OU 1603 IUINV ...
Page 80: ...Troubleshooting Electrical Control System 121 2 4 2 3 Up down panel is not closed ...
Page 88: ...Troubleshooting Electrical Control System 129 2 4 3 8 P0 malfunction ...
Page 89: ...Troubleshooting 130 Electrical Control System 2 4 3 9 P1 malfunction ...
Page 90: ...Troubleshooting Electrical Control System 131 2 4 3 10 P2 malfunction ...
Page 91: ...Troubleshooting 132 Electrical Control System 2 4 3 11 P3 malfunction ...