Electrical Control Function
Electrical Control System
107
4-Way valve
Indoor fan
Outdoor fan
480P
PMV
PMV running
8 mins with 300P
Compressor
10S
30S
TimeA
10S
no longer than 10min
Condition of ending defrosting:
If any one of following items is satisfied, defrosting will stop and the machine will turn to normal heating
mode.
①
The defrosting time achieves 10min;
②
T3
≥
15
℃
;
③
T3
≥
7
℃
for 60seconds.
1.3.3.5 High evaporator coil temp.T2 protection:
T2>60
℃
, the compressor will stop and restart when T2<54
℃
.
1.3.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30
℃
.
In auto mode, the machine will choose cooling, heating or fan-only mode according to
∆
T (
∆
T =T1-Ts).
∆
T=T1-Ts Running
mode
∆
T
≥
2
℃
Cooling
-1
≤∆
T<2
℃
Fan-only
∆
T<-1
℃
Heating
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will keep stopping for 15
minutes and then choose mode according to T1-Ts.
If the setting temperature is modified, the machine will choose running function again.
1.3.5 Drying mode
Drying mode works the same as cooling mode in low speed.
Summary of Contents for CCT 140IUINV
Page 13: ...Service Space Super Slim Cassette Type 13 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 14: ...Wiring Diagrams 14 Super Slim Cassette Type 4 Wiring Diagram CCT140 IUINV CCT160 IUINV ...
Page 26: ...Wiring Diagrams Duct Type 27 4 Wiring Diagrams DCT140 IUINV DCT160 IUINV ...
Page 32: ...Field Wiring Duct Type 33 10 Field Wiring ...
Page 35: ...Service Space Ceiling Floor Type 37 3 Service Space ...
Page 36: ...Wiring Diagrams 38 Ceiling Floor Type 4 Wiring Diagrams CFT140 IUINV CFT160 IUINV ...
Page 41: ...Field Wiring Ceiling Floor Type 43 9 Field Wiring ...
Page 45: ...Service Space GA Floor standing Type 47 3 Service Space ...
Page 46: ...Wiring Diagrams 48 GA Floor standing Type 4 Wiring Diagrams FS140IUINV FS160IUINV ...
Page 56: ...Wiring Diagrams 70 Outdoor Units OU 1403 IUINV OU 1603 IUINV ...
Page 80: ...Troubleshooting Electrical Control System 121 2 4 2 3 Up down panel is not closed ...
Page 88: ...Troubleshooting Electrical Control System 129 2 4 3 8 P0 malfunction ...
Page 89: ...Troubleshooting 130 Electrical Control System 2 4 3 9 P1 malfunction ...
Page 90: ...Troubleshooting Electrical Control System 131 2 4 3 10 P2 malfunction ...
Page 91: ...Troubleshooting 132 Electrical Control System 2 4 3 11 P3 malfunction ...