13
☞
Fig. 3 Template
After using the installation template as a guide for the
drilling of the hole for the exhaust pipe, the heater can
be installed normally, according to the procedure in the
illustration.
If the template is lost or the heater has to be moved,
these are the dimensions and locations of the holes for
the fuel pipe and exhaust pipe.
Do not remove any components from the
heater. Always contact your dealer if repairs
are required.
If the electricity cable is damaged, this may
only be replaced with type H05 VV-F and by
a recognised installer.
638
244
202
Hole for wall bracket
220
552
286
264
99
80
86
212
61
Contre of the feed-
through component
R110
Fig. 2 Gaps heater/exhaust pipe
Important:
The gap with the ground must be enlarged in areas
subject to heavy snowfall.
Important:
A windbreaker may be necessary in open areas that
are subjected to strong winds.
Fig. 1 (continued) gaps heater/exhaust pipe
Combustible object
Not less than 60 cm
Combustible object
Noncombustible object
Not less than 60 cm
Not less than 30 cm
Flue pipe
* Not less than 20 cm
45˚
* Be sure this
clearance will
be maintained
after snowfalls,
etc.
Not less than
45 cm
Frontal obstruction
45 cm
or more
Snow-covered surface or ground
50 cm
or more
Must be higher
Extension tube of
max. 2.5 metres
Snow
Windbreaker
Not less
that
45 cm
Strong wind
Distance from
exhaust pipe to
windbreaker
minimum 45 cm
Not less than 45 cm