4 Parameterization via TRWinProg
Danger of personal injury and damage to property exists if the
measurement system is restarted after positioning in the de-energized
state by shifting of the zero point!
If the number of revolutions is not an exponent of 2 or is >4096, it can occur, if
more than 512 revolutions are made in the de-energized state, that the zero
point of the multi-turn measuring system is lost!
•
Ensure that the quotient of
Revolutions Numerator / Revolutions
Denominator
is an exponent of 2 of the group 2
0
, 2
1
, 2
2
…2
12
(1, 2, 4…4096).
or
•
Ensure that every positioning in the de-energized state for a multi-turn
measuring system is within 512 revolutions.
4.1 Basic parameters
4.1.1 Count direction
Selection
Description
Default
Increasing
Measuring system position increasing clockwise
(view onto the shaft)
X
Decreasing
Measuring system position decreasing clockwise
(view onto the shaft)
4.1.2 Scaling parameters
The scaling parameters can be used to change the physical resolution of the
measuring system. The measuring system supports the gearbox function for round
axes.
This means that the
Measuring units per revolution
and the quotient of
Revolutions
numerator / Revolutions
denominator
can be a decimal number.
The position value output is calculated with a zero point correction, the count direction
set and the gearbox parameter entered.