4.2.5 For the speed output valid parameters
Start and final value in 1/Min:
With the parameters
start value in 1/Min
and
final value in 1/Min
the n-range can be defined within the speed limits of -6000 1/Min and +6000 1/Min.
Thereby the start value must be defined smaller than the final value.
Start and final value in mV:
With the parameters
start value in mV
and
final value in mV
it can be
defined the U-range within the maximum voltage values. Thereby the start value must
be defined smaller than the final value.
Example:
Figure 10: Definition of the active range (voltage / speed)
Legend
U
O
= actual measured voltage output [V] *
U
max
= maximal possible voltage output [V] *
U
SV
= programmed
start value
of the voltage
in mV
*
U
FV
= programmed
final value
of the voltage
in mV
*
n
= actual speed of the measuring system [1/Min] *
n
max
= maximal permissible speed of the measuring system [1/Min] *
n
SV
= programmed
start value
of the speed
in 1/Min
*
n
FV
= programmed
final value
of the speed
in 1/Min
*
* signed