7.2.1.1 Station status 1
S
ta
nda
rd
di
a
gnos
is
,
by
te
1
Bit 7
Master_Lock
Slave has been parameterized
by another master (bit is set by
master)
Bit 6
Parameter_Fault
The last parameterization
message to have been sent was
rejected by the slave
Bit 5
Invalid_Slave_Response
Set by the master if the slave
does not respond
Bit 4
Not_Supported
Slave does not support the
requested functions
Bit 3
Ext_Diag
Bit = 1 means that there is an
extended diagnostic message
from the slave
Bit 2
Slave_Cfg_Chk_Fault
The configuration identifier(s)
sent by the master was/were
rejected by the slave
Bit 1
Station_Not_Ready
Slave is not ready to exchange
cyclical data
Bit 0
Station_Non_Existent
The slave has been configured
but is not present on the bus
7.2.1.2 Station status 2
S
ta
nda
rd
di
a
gnos
is
,
by
te
2
Bit 7
Deactivated
Slave has been deleted from the
poll list by the master
Bit 6
Reserviert
Bit 5
Sync_Mode
Set by slave on receipt of SYNC
command
Bit 4
Freeze_Mode
Set by slave on receipt of
FREEZE command
Bit 3
WD_On
Slave watchdog is activated
Bit 2
Slave_Status
Always set for slaves
Bit 1
Stat_Diag
Static diagnosis
Bit 0
Prm_Req
The slave sets this bit if it has to
be re-parameterized and re-
configured.
7.2.1.3 Station status 3
Standard diagnosis, byte 3
Bit 7
Ext_Diag_Overflow
Overflow in extended diagnosis
Bit 6 - 0
Reserviert