7.9 Object 100Ch: Guard time
The objects at index 100Ch and 100Dh include the guard time in milli-seconds and the
life time factor. The life time factor multiplied with the guard time gives the live time for
the Node Guarding Protocol. Default value = 0.
Unsigned16
Guard Time
Byte 0
Byte 1
2
7
to 2
0
2
15
to 2
8
7.10 Object 100Dh: Life time factor
The life time factor multiplied with the guard time gives the life time for the Node
Guarding Protocol. Default value = 0.
Unsigned8
Life Time Factor
Byte 0
2
7
to 2
0