7.12 Object 1011h: Restore default parameters
This object supports the restoring of the CAN communication parameters and the
device specific parameters.
Index
Sub-Index
Comment
Type
Attribute
1011h
0
largest supported Sub-Index = 3
Unsigned8
ro
1
restore all default parameters
Unsigned32 rw
2
restore communication default
parameters, indices 1xxxh
Unsigned32 rw
3
restore device specific parame-
ters, indices 2xxxh and 6xxxh
Unsigned32 rw
In order to avoid restoring of parameters by mistake, restoring is only executed when
a specific signature is written to the appropriat sub-index. The signature is "load".
MSB
LSB
d
a
o
l
64h
61h
6Fh
6Ch
On reception of the correct signature, the device restores the appropriate default
parameters. If restoring failed, the device responds with abort domain transfer: Error
code 0606 0000h.
If a wrong signature is written, the device refuses to restore the defaults and responds
with abort domain transfer: 0800 0020h.
The default values will be set valid after the device is reset: NMT service RESET
NODE (0x81) for sub-index from 1 to 3, NMT service RESET COMMUNICATION
(0x82) for sub-index 2, or power cycled.
On read access to the appropriate sub-index the device provides information about its
default parameter restoring capability:
MSB
LSB
Bits
31-1
0
Value
= 0
1
Bit 0 = 1: Device supports restoring of default parameters.