11 Causes of faults and remedies
11.1 Optical displays
Assignment of the LEDs see chapter “Bus status”, page 146.
Green LED
Cause
Remedy
Off
Voltage supply absent or was
fallen below
-
Check voltage supply, wiring
-
Does the voltage supply is in the permitted
range?
Hardware fault,
measuring system defective
Replace measuring system
Flashing,
1 Hz
Measuring system is in PRE-
OPERATIONAL mode
-
Try to switch the measuring system into
OPERATIONAL state
-
Adjusted baud rate must agree with the master
baud rate!
On
Measuring system is in
OPERATIONAL mode and is
ready for operation
-
Table 13: Display states of the status LED
Red LED
Cause
Remedy
Off
No error
-
On
Measuring system could not
detected any magnet
- Guarantee that all magnets are in the valid
measuring range.
- Guarantee that the minimum distance is kept
between the magnets.
- Guarantee that the configured number of
magnets agrees with the operated number.
Table 14: Display states of the error LED
Green LED
Red LED
Cause
Remedy
Flashing,
10 Hz
Flashing,
10 Hz
Measuring system is in LMT/LSS
CONFIGURATION mode
Save LMT/LSS configuration,
measuring system is switched
into PRE-OPERATIONAL mode
Table 15: Display states of the status LED / error LED