8.5.8 Error output value
Specification of the Error value which is transferred as data value if a fault is present.
See parameter
Error output --> Error output value
Availability
TR-Mode
X
TR-Mode extended
X
Lower limit
0xFE D3 A1 50 (
–19 685 040)
Upper limit
0x01 2C 5E B0 (+19 685 040)
Default
0x00 00 00 00
8.5.9 Digital Input / Output 1
Definition of the function for the programmable Digital Input DI1.
Availability
TR-Mode
TR-Mode extended
X
not supported!
Selection
Description
Default
Output:
Digital Output 1
Digital Input DI1 = inactive,
Digital Output DO1 = active
The configuration of the output is carried out in
accordance with the parameters
Digital Output 1
ON/OFF
, page 121.
Output circuit see chap. 6.3.2 on page 95.
X
Input:
Single
measurement
Digital Input DI1 = active,
Digital Output DO1 = inactive
Input circuit see chap. 6.3.1 on page 95.
With the positive edge at the input a single distance
measurement is executed. For that purpose the
parameter “Measuring cycle” must be adjusted to the
value “255” decimal. The position value will be stored,
until the next triggering is performed.
Input:
Continuous
measurement
Digital Input DI1 = active,
Digital Output DO1 = inactive
Input circuit see chap. 6.3.1 on page 95.
With the positive edge at the input the distance
measurement is executed. The distance measuring is
continued as long as the falling edge of the present signal
level is recognized.
Note:
For
that purpose the parameter “Measuring cycle” must
be adjusted to the value “255” decimal. The distance
measuring is performed automatically as fast as possible.