6.3.3.15.1 Scaling: Measuring step [nm]
Alternatively, this parameter can also be set during operation via acyclic parameter access to the
scaling function
PNU 65006
, see page 138.
Function, if parameter
Scaling: Total Measuring Range
= 0:
The total number of steps over the whole measurement range of the measuring system is defined, via
the measuring length stored in the measuring system and the resolution set here.
Selection
Description
Default
1000
Resolution = 1 µm per step
X
2000
Resolution = 2 µm per step
5000
Resolution = 5 µm per step
10 000
Resolution = 10 µm per step
50 000
Resolution = 50 µm per step
100 000
Resolution = 100 µm per step
1000 000
Resolution = 1 mm per step
6.3.3.15.2 Scaling: Total Measuring Range
Alternatively, this parameter can also be set during operation via acyclic parameter access to the
scaling function
PNU 65007
, see 138.
Function, if parameter
Scaling: Total Measuring Range
= 0:
The total number of steps over the whole measurement range of the measuring system is defined, via
the measuring length stored in the measuring system and the resolution set under the parameter
Scaling: Measuring step [nm]
.
Function, if parameter
Scaling: Total Measuring Range
> 0:
The resolution of the measuring system is defined in [µm], via the measuring length stored in the
measuring system and the total number of steps over the whole measurement range set here. The
setting under the parameter
Scaling: Measuring step [nm]
is ignored in this case.
Data type
Unsigned32
Lower limit
0 steps
Upper limit
4 294 967 295 steps
Default
0 steps
6.3.3.16 Tolerated sign-of-life errors (V4.2)
Alternatively, this parameter can also be set during operation via acyclic parameter access to the
master sign-of-life error function
PNU 925
, see page 140.
The max. number of permissible errors of the master sign-of-life counter is defined with this
parameter. The parameter
Compatibility Mode V3.1
must be set to
disable
for this purpose. If
the max. number of permissible errors is exceeded, the error code
0x0F02
is transmitted instead of
the position via signal
G1_XIST2
.
Data type
Unsigned8
Lower limit
0, Function is switched off
Upper limit
255
Default
1