Parameterization and Configuration
TR-Electronic GmbH 2018, All Rights Reserved
Printed in the Federal Republic of Germany
Page 150 of 167
TR - ELA - BA - DGB - 0027 - 03
11/12/2019
6.4.1.1 Interpolation
Selection
Value Description
Default
disable
0
A new position value is output according to the internal
measuring system cycle time. If the bus cycle time
corresponds to the internal measuring system cycle time, a
new position value will also be output per bus cycle in this
case.
X
enable
1
If the internal measuring system cycle time is much greater
than the bus cycle time, it may be useful to switch on the
interpolation.
Recommendation: Switch on interpolation for bus cycle
times ≤ 4 ms
Intermediate position values can then be calculated through
internal measured value processing. These calculated
position values have a much smaller cycle time than the
internal measuring system cycle time.
6.4.1.2 Code Sequence
The code sequence defines whether rising or falling position values are output by the measuring
system, when the magnet is moved to the end of the bar.
Selection
Value Description
Default
Rising
0
Rising position values
X
Decreasing
1
Falling position values
6.4.1.3 Scaling: Measuring step [nm]
The total number of steps over the whole measurement range of the measuring system is defined, via
the measuring length stored in the measuring system and the resolution set here.
Selection
Description
Default
1000
Resolution = 1 µm per step
X
2000
Resolution = 2 µm per step
5000
Resolution = 5 µm per step
10 000
Resolution = 10 µm per step
50 000
Resolution = 50 µm per step
100 000
Resolution = 100 µm per step
1000 000
Resolution = 1 mm per step
Measurement length in steps =
Measuring length [mm]
Resolution [mm]