Parameterization and configuration
TR-Electronic GmbH 2011, All Rights Reserved
Printed in the Federal Republic of Germany
Page 114 of 131
TR - ECE - BA - DGB - 0089 - 04
02/03/2016
7.9.6 Scaling function
Availability
PNO CLASS1 16 + 32
PNO CLASS2 16 + 32
X
TR-Mode Position
TR-Mode Po Rpm.
not supported!
not supported!
not supported!
Defines whether the position is scaled according to the parameters
-
"Measuring units per revolution"
-
"Total measuring range"
If Class 2 is switched off, the position value cannot be scaled or adjusted.
7.9.7 Scaling parameter PNO CLASS 2
Maximum steps per revolution: ≤ 8192
If higher resolutions are required, one of the TR-Modes must be used
If the scaling parameters are activated with the
Scaling function
, the physical
resolution of the measuring system can be changed. The position value output is
binary decoded and is calculated with a zero point correction and the count direction
set. The measuring system does not support decimal numbers in this configuration or
numbers of revolutions (gearbox function) deviating from exponents of 2.
7.9.7.1 Steps per revolution
Defines how many steps the measuring system outputs for one revolution of the
measuring system shaft.
lower limit
1 step / revolution
upper limit
8192 steps per revolution (Max. value see nameplate)
default
4096