PROFIBUS-DP RS485 Installation / Pre-commissioning
TR-Electronic GmbH 2011, All Rights Reserved
Printed in the Federal Republic of Germany
Page 80 of 131
TR - ECE - BA - DGB - 0089 - 04
02/03/2016
5.1.2 Cable type
“PROFIBUS ECOFAST Hybrid Cable” with 4x1.5+2x0.64 mm
2
Devices which have the following marking on the name plate are equipped with this
cable:
●
II 3G
…
;
II 2D
…
Parameter
Description
Illustration
TR Order-No.:
64-200-156X
Attenuation factor per length
- at 9.6 kHz / maximal
- at 38.4 kHz / maximal
- at 4 MHz / maximal
- at 16 MHz / maximal
0.0030 dB/m
0.0040 dB/m
0.025 dB/m
0.049 dB/m
Wave impedance
150
±10% at 3...20 MHz
Loop resistance
138
/km
Shielding resistance
15
/km
Capacity
30 pF/m at 1 kHz
Conductor cross-section,
power wire conductor
1.5 mm
2
Wire diameter
2.56 mm
Cable diameter
11 mm ±0.3 mm
Conductor insulation
PE
Jacket
PUR
Bending radius, moved
≥ 7.5x outer diameter
Number of bending cycles
5000000 at 2.5 m/s
2
Tensile loading
≤ 300 N
Weighting
150 kg/km
Temperature range
-
40…+60 °C
Protection class IP
IP 65
Reaction to fire
flame retardant,
IEC 60332-1
Resistance against
- Mineral oil
- Grease
conditionally resistant
Resistance against
- UV radiation
conditionally resistant
Product characteristic
free of halogens and
silicone