background image

           TLED-XPF

INSTALLATION INSTRUCTIONS

800.533.3948 

 www.barronltg.com 

2

20070081 REV 2 - 10/16

2. Feed power cord leads from fixture through the appropriate opening in trunnion. 

3. Electrical connection should be made inside an approved junction box. Fixture auto adjust for voltages between 

    120VAC - 277VAC

    a. Connect the line fixture brown lead to the black supply lead.

    b. Connect the common fixture blue lead to the white supply lead.

    c. Connect the ground yellow/green lead from the sevice to green grounding screw. 

4. Use approved connectors to connect fixture leads to supply leads and make wire splices inside an approved 

    electrical box. 

5.  Set desired fixture angle by loosing positioning screws and rotating trunnion to desired angle. Then tighten 

     positioning screws.

IMPORTANT

To weather-proof your outdoor installation, be sure to seal all holes in fixture housing. (Mounting, conduit, plugs, and 

photo controls, etc) with silicone sealant. 

TROUBLESHOOTING CHECKLIST

TLED-XPF does not turn “ON”

1. Check incoming voltage to LED driver. Must be at least a minimum of 120VAC and no greater than 277VAC.

2. Are all the LEDs on the light engine “OFF”? If so, LED driver may be defective. Using a voltmeter, check to see if 

    voltage is present at the output of the power supply. If low or no voltage, then replace power supply. 

3. If any individual LEDs are “OFF” the LED light engine is defective. Please have the serial number off the light engine 

    available when you contact technical support.

Reviews: