Site Preparation Guide 
TRAK VMC7si  

                                                                                                                                           

F16467-62 | Rev 8/3/2021 

Page 6 of 7 

 

Electrical Connections 

Main Power to the Machine Connections 

The 3 phase 480 volt (432 to 528 V is acceptable) or 208 volt (200 

 240 V is acceptable) is connected to L1, L2 and 

L3 at the main power switch inside the electrical box. Connect the ground wire as shown in the figure 10.   

 

Figure 9 

 Connect the Ground Wire 

Machine Grounding 

It is strongly recommended that the machine be earth grounded. A dedicated copper rod 8 feet or so in length 

should be driven into the ground near the VMCsi. A ground wire should then be run from the location shown in 
figure 9. The copper wire should exit the electrical cabinet in the mid left hand side as shown in figure 10. Make sure 
the foam where the copper wire goes through seals the cabinet from external debris. The wire should be 6 gage in 

size.  

 
 
 
 
 

 

 
 
 
 
 
 

 
 