Page 7
TEF 4600 CONTROL SYSTEM -
INSTALLATION AND USER MANUAL
10.2.2 Activate (Manual activation)
The Activate function is activated/deactivated by press-
ing and holding the Activate button for 2 seconds.
Manual activation of Status lights will keep the Status
lights activate until:
•
Manual deactivation.
•
Suppress mode activation.
•
Activate is not possible if the system is Suppressed or
if external Fire & Gas signal has activated the system.
10.2.3 Dim
The Dim function is activated/deactivated by pressing
and holding the Dim button for 2 seconds.
Dim of Status lights will keep the Status lights dimmed
until:
•
Dim Timeout specified time has elapsed. (only
applicable if Dim Timeout is enabled in the Setup
screen.)
•
Suppress mode activation.
•
Dim mode deactivation.
•
Manual Activation.
•
Dim is not possible if the system is Suppressed.
10.2.4 Activation Timeout
Activation timeout will deactivate the Status light system
when the timer has elapsed. Default value is 30 minutes.
The Activation timeout is enabled in the Setup screen.
10.2.5 Dim Timeout
Dim timeout will deactivate the dimming function when
the timer has elapsed. Default value is 30 minutes. The
Dim timeout is enabled in the Setup screen.
10.2.6 Inspection Interval
Inspection interval is a time span of days which, when
counted down, will trigger an Inspection Required indi-
cator in the Status Light screen. The Operator can man-
ually enter the number of days for Inspection required
prompt. To reset the inspection timer the operator needs
to press the Inspection Reset button.
10.2.7 Status light Fault indicators
There are fiver Status Light fault indicators:
•
Main Light 1 Fault:
Blinking indicates light is
connected but error is present. Steady light indicates
Light is disconnected.
•
Main Light 2 Fault:
Blinking indicates light is
connected but error is present. Steady light indicates
Light is disconnected.
•
Repeater Light 1 Fault:
Blinking indicates light is
connected but error is present. Steady light indicates
Light is disconnected.
•
Repeater Light 2 Fault:
Blinking indicates light is
connected but error is present. Steady light indicates
Light is disconnected.
•
MCB Fault:
Steady light indicates error is present on
24VDC Power Supply distribution circuit breaker.