Copyright © 2005
– 2021 R. STAHL TRANBERG AS. All rights reserved. Page 16 of 38
Fields are the same as for systems delivered after November 1
st
2017, except the
checksum calculation:
Checksum H: The ‘hundreds’ digit of the checksum (e.g. 1 if the che cksum is 120).
Checksum M: The ‘tens’ digit of the checksum (e.g. 2 if the checksum is 120).
Checksum L: The ‘ones’ digit of the checksum (e.g. 0 if the checksum is 120).
When calculating the checksum, the ASCII value of each character has been used. The
checksum is the XOR-ing of all characters sent, except the leading $-character, the
commas and the final carriage return and new line characters.
Channel 8
– Channel 1 detailed information:
The data in the corresponding positions Channel 8
– Channel 1 depends on which type
of module the message is sent from . See the table below for details.
Module type
Ch. 8
Ch. 7
Ch. 6
Ch. 5
Ch. 4
Ch. 3
Ch. 2
Ch. 1
Type B, without
current sensing
Relay 8
Relay 7
Relay 6
Relay 5
Relay 4
Relay 3
Relay 2
Relay 1
Output states, see table below
Type C, with
current sensing
Relay 8
Relay 7
Relay 6
Relay 5
Relay 4
Relay 3
Relay 2
Relay 1
Output states, see table below
Type D
combined
dimmer and
flasher module
Output state,
see table
below
Dim
or
Flash
value
0
0
0
0
0
0
Output state:
Value
Description
Applies to
Type B
Applies to
Type C
Applies to
Type D
‘0’
Disregard
Y
Y
Y
‘1’
Off
Y
Y
Y
‘2’
On, but no current
N
Y
Y
‘3’
Not used, disregard
N
Y
Y
‘4’
On, current ok
Y
Y
Y
‘5’
Manual override, no current
N
Y
Y
‘6’
Manual override, current ok
N
Y
Y
Dimmer and flasher value:
Value
Dimmer level
(%)
Flasher rate
(blink / min.)
‘0’
0 (off)
0 (off)
‘1’
15
30
‘2’
30
60
‘3’
45
90
‘4’
60
120
‘5’
75
260
‘6’
90
180
‘7’
100 (max)
200