Data clearing
To clear all values in the panel, do the following:
Remove power from the panel.
Make a note of the setting of the dial COL at the rear side. Set it to position 0.
Reconnect power to the panel again.
Wait 15 seconds.
Remove power from the panel.
Set the dial COL back to its original position.
Reconnect power to the panel again.
Data retention time
The non-volatile memory may be written to 100,000 times and will keep the data for 40
years.
Connections
Power
The 24VDC power is connected on the rear of the panels using regular screw terminals.
RS-485 network
The network is connected on the rear of the panels using RJ-45 terminals.