Chapter VI.
Output modules
Section 6.01
Overview
The following output modules are available:
Part No.
Voltage
Monitoring
of outputs
Description
4900 910
24V AC/DC
Yes
Fuses relay output module, 4 outputs. Max. 40W filament
lamp load per output.
4900 911
24V AC/DC
Yes
Fuses relay output module, 8 outputs. Max. 40W filament
lamp load per output.
4900 912
24V DC
Yes
Fuses relay output module, 4 outputs. Max. 20W LED
lamp load per output.
See note below.
4900 913
24V DC
Yes
Fuses relay output module, 8 outputs. Max. 20W LED
lamp load per output.
See note below.
4900 920
115/230V AC
Yes
Fuses relay output module, 4 outputs. Max. 85W filament
lamp load per output.
4900 921
115/230V AC
Yes
Fuses relay output module, 8 outputs. Max. 85W filament
lamp load per output.
4900 930
N/A
No
Relay output module, 8 potential free C/O outputs.
4900 935
N/A, 24VDC
No
Relay output / digital input module. 4 potential free C/O
outputs. 4 digital (24VDC) inputs.
4900 940
115/230V AC
Yes
Fused relay output module, 1 output. Dimming output.
4900 950
115/230V AC
Yes
Fused relay output module, 1(2) output. Blinking output.
Note, output modules for LED navigation lights: Alarm threshold level: 34mA. Connected
LED navigation lights shall be self-monitored and have built in life time control. In normal
operation current consumption shall be >38mA. In “alarm” state, current consumption
shall be <31mA.
Common hardware
CPU
All modules use a dedicated microcontroller with onboard memory.
Power supply
The power feed is supervised by the Master CPU and signaled to the connected nodes
via the RS-485 network. Up to 4 power feeds are possible, which are connected in
parallel via a set of diodes. The combination output forms a common power supply for
the connected nodes.
Address of modules
The address of the modules are preset at delivery. Two dials labeled ADR LSB and
ADR MSB are used to set the address. Range is from 0 through 7 only on each dial,
and the setting is in octal values. Never change the addresses, and if replacing a
module, please ensure that the address of the new module is identical to the replaced
module.