background image

18-GE08D1-6

3

Installer’s Guide

CAUTION

!

For air handlers not equipped with a factory installed
electric heater, a field installed heater is available from
Trane. Only heaters built by Trane are approved for use
in the air handler. These heaters have been designed
and tested in accordance with UL standards to provide
safe and reliable operation. A list of approved heaters
is provided on the air handler rating nameplate.  Heat-
ers that are not factory approved could cause damage
and are not covered under equipment warranty.

NOTE: If air handler is used WITHOUT a supplementary
electric heater, a sheetmetal plate is required to cover
the open hole in the airflow system. See Figure 2. Also
seal the cabinet air tight where the wire enters.

10. If the unit is installed without a return air duct, ap-

plicable local codes may limit this air handler to in-
stallation only in a single story residence and
within conditioned space.

11. If the outdoor unit is to be installed later, or by oth-

ers, then installation of the air handler must be
made to allow access for refrigerant lines, or attach
refrigerant lines to air handler when installing.

12. Make sure there are provisions for installing con-

densate drain lines.

13. If side, front or rear return is required, air handler

must be elevated or placed on a plenum
(TAYPLNM100 for 2/4TEC3F18 - 48B, 2/4TEC3F60B
or TAYPLNM101 for 2/4TEC3F55B). Connecting re-
turn duct directly to the side, front or rear of the
cabinet is not approved.

14. Route refrigerant and condensate drain lines away

from air handler so they do not interfere with ac-
cess panels and filters.

15. When external accessories are used, the additional

height and width requirements must be considered
in the overall space needed.

16. These units are not approved for outdoor installa-

tion.

17. These units are approved for draw-through appli-

cation only.

NOTE: No atomizing style humidifier is allowed in the
return plenum with the use of this unit.

18.

Flow-through Bypass Humidifiers

Excessive bypass air may cause water blow-off,
which will adversely affect system operation and air
cleaner performance. To verify bypass airflow, fol-
low the Bypass Humidifier Pre-Installation Check-
out and Set-Up Procedures available through your
local distributor. Ask for publication number 18-
CH37D1-1.

Steam and Flow-through Fan Power Duct-
mounted Humidifiers

Follow the humidifier installation instructions.
These should only be installed on the supply air
side of the system.

B. TWO PIECE CABINET DISASSEMBLY

(OPTIONAL)

NOTE: For easier installation into tight areas, the 4
and 5 ton air handlers can be disassembled and reas-
sembled after moved to an attic or other space.

Steps for disassembly and reassembly (See Figures 3
and 4)
1.

Disconnect wiring.

2.

Remove center bracket.

3.

Remove blower assembly.

4.

Remove coil.

5.

Cut foil tape - minimum 3" foil tape.

6.

Remove top 8 screws. See Figure 3.

7.

Lift upper section.

8.

Set air handler in place.

9.

Attach screws - insure gaskets are aligned
along flange.

10.

Use foil tape to seal - use minimum 3" foil tape.

11.

Insert coil.

12.

Reinstall blower assembly.

13.

Reinstall center bracket.

14.

Reconnect wiring.

NOTE: In Downflow, remove coil before blower by
reversing steps 4 and 5.

C. UNIT INSTALLATION

UPFLOW

a.

For maximum efficiency

, the horizontal drip

tray should be removed. See Figures 6, 7 and
8. Drip tray removal requires that the coil be
removed by sliding the coil out on the coil
channel supports. The drip tray is detached by
removing the two screws at the drain pan and
the two screws holding the two brackets at the

From Dwg. 21B140413

4"

6"

17"

1"

3/8"

1/4" HOLES (4)

ACCESSORY BAY99X123

IF AIRHANDLER IS USED 

WITHOUT

 A FACTORY FURNISHED

SUPPLEMENTARY HEATER, A PLATE IS REQUIRED TO COVER
THE OPEN HOLE IN THE AIR FLOW SYSTEM

2

Summary of Contents for 2/4TEC3F18B1000A

Page 1: ...These instructions do not cover all variations in systems or provide for every possible contingency Should fur ther information be desired or particular problems arise which are not covered sufficient...

Page 2: ...supply air if the minimum clearances to combustible materials and service access are observed the above installations are suitable This area may also be used for other purposes includ ing an electric...

Page 3: ...door installa tion 17 These units are approved for draw through appli cation only NOTE No atomizing style humidifier is allowed in the return plenum with the use of this unit 18 Flow through Bypass Hu...

Page 4: ...utline drawing e On units with sheetmetal returns Return ple num should be flanged Sheetmetal screws must be 1 2 in length or shorter f No sheetmetal screws may be used to attach re turn duct work on...

Page 5: ...to coil with gasket material compressed against the coil f Install the water blow off baffles provided on each side of the coil with the flange at the top as shown in Figure 9 The bottom of the baffl...

Page 6: ...hould not ex ceed the face velocity of the filter being used The factory installed filter should then be removed from the unit Remove the factory installed baffle assembly from the apex of the coil by...

Page 7: ...event sagging The service access must remain unobstructed If the unit is sup ported along the length of the front and back with rails the air handler only needs to be sus pended at both ends See Figur...

Page 8: ...revent air leakage NOTE No sheetmetal screws may be used to attach re turn ductwork on the side NOTE On units with sheetmetal returns Return plenum should be flanged Sheetmetal screws must be 1 2 in l...

Page 9: ...lean out tee or cross be installed in the primary drain line for future maintenance See Figures 15 16 4 Do not use reducing fittings in the condensate drain lines 2 Field supplied tubing should be cut...

Page 10: ...RING 1 Connect wiring between indoor unit outdoor unit and Comfort Control The use of color coded low voltage wires is recommended 2 Field wiring diagrams are provided which show the low voltage wirin...

Page 11: ...18 GE08D1 7 11 Installer s Guide 2 4TEC AIR HANDLER WITH HEAT PUMP WITH SUPPLEMENTAL HEAT From Dwg B801082 Rev 2...

Page 12: ...12 18 GE08D1 7 Installer s Guide 2 4TEC AIR HANDLERS WITH SINGLE SPEED COOLING UNIT 1 STAGE HEAT From Dwg B801083 Rev 2...

Page 13: ...18 GE08D1 7 13 Installer s Guide 2 4TEC AIR HANDLER WITH SINGLE SPEED COOLING UNIT 2 STAGE HEAT From Dwg B801081 Rev 2...

Page 14: ...14 18 GE08D1 7 Installer s Guide OUTLINE DRAWING FOR 2 4TEC3F18 60B...

Page 15: ...ONAL DATA H W 21 0 2 4TEC3F48B 60B are two piece cabinets MODEL H W 2 4TEC3F18B 43 00 21 50 2 4TEC3F24B 43 00 21 50 2 4TEC3F30B 45 00 21 50 2 4TEC3F36B 45 00 21 50 2 4TEC3F42C 51 75 23 50 2 4TEC3F48B...

Page 16: ...ode 3 Make sure unit suspension if used is secure and that there are no tools or loose debris in around or on top of the unit 4 Check all duct outlets they must be open and unrestricted 5 Check drain...

Reviews: