background image

© 2010 Trane

18-BC52D5-5

Installer’s Guide

control box (access panels) and any other side requiring
service access to meet National Electrical Code. Also, the
unit location must be far enough away from any struc-
ture to prevent excess roof run-off water from pouring
directly on the unit. Do not locate unit(s) close to
bedroom(s).

4. The top discharge area must be unrestricted for at least

five (5) feet above the unit.

5. When the outdoor unit is mounted on a roof, be sure the

roof will support the unit’s weight. Properly selected
isolation is recommended to prevent transmission to the
building structure.

6. The maximum length of refrigerant lines from outdoor to

indoor unit should NOT exceed eighty (80) feet.

7. If outdoor unit is mounted above the air handler, maxi-

mum lift should not exceed sixty (60) feet (suction line).
If air handler is mounted above condensing unit, maxi-
mum lift should not exceed sixty (60) feet (liquid line).

8. Locate and install indoor coil or air handler in accor-

dance with instruction included with that unit.

C. ACCUTRON™ FLOW CONTROL VALVE

If the indoor unit System Refrigerant Flow control is an
Accutron™ orifice and check valve assembly, an orifice size
change may be necessary.

The outdoor model determines the required orifice size.
Check the listed orifice size on nameplate of the selected
outdoor model. If the indoor unit is factory shipped with a
different orifice size, the orifice must be changed to obtain
system rated performance.

IMPORTANT:

The outdoor unit is shipped with the proper size orifice and a
stick-on orifice size label in an envelope attached to the outdoor
unit. Outdoor unit nameplate will have correct orifice size
specified as BAYFCCV --- A for rated performance.

D. INSTALLING REFRIGERANT LINES

Condensing units have provisions for flare connections.

Pressure taps are provided on the service valves of outdoor
unit for compressor suction and liquid pressures.

The indoor end of the recommended refrigerant line sets may
be straight or with a 90 degree bend, depending upon
situation requirements. This should be thoroughly checked
out before ordering refrigerant line sets.

The gas line must always be insulated.

IMPORTANT:

The unit has a NITROGEN holding charge which will need to
be evacuated before charging per local system application
requirement.

Refrigerant charge adjustment is necessary. 

Use the

Charging Charts in the outdoor unit Service Facts.

1. Determine the most practical way to run the lines.

2. Consider types of bends to be made and space

limitations.

NOTE:
Large diameter tubing will be very difficult to rebend once it
has been shaped.

3. Determine the best starting point for routing the refriger-

ant tubing — INSIDE OR OUTSIDE THE STRUCTURE.

4. Provide a pull-thru hole of sufficient size to allow both

liquid and gas lines.

5. Be sure the tubing is of sufficient length.

6. Uncoil the tubing — do not kink or dent.

7. Route the tubing making all required bends and

properly secure the tubing before making connections.

8. To prevent a noise within the building structure due to

vibration transmission from the refrigerant lines, the
following precautions should be taken:

BASEPAN TAB REMOVAL

2

BRAZE TYPE INDOOR END

3

SEALING CAP

ADAPTER

FLOW CONTROL
CHECK VALVE
(F.C.C.V.) ORIFICE

FIELD SUPPLIED
LIQUID LINE

AS SHIPPED

BODY

ACCUTRON

TM

COMPONENTS

4

 LIQUIID LINE SERVICE VALVE

Summary of Contents for 2TWB0012-036AA

Page 1: ...rise which are not covered sufficiently for the purchaser s purposes the matter should be referred to your installing dealer or local distributor A GENERAL The following instructions cover 2TWB0012 036AA Heat Pump Units NOTE These outdoor units may be used with indoor units equipped with Thermostatic Expansion Valve or Accutron Flow Control Check Valve F C C V assembly for refrigerant flow control...

Page 2: ...el in an envelope attached to the outdoor unit Outdoor unit nameplate will have correct orifice size specified as BAYFCCV A for rated performance D INSTALLING REFRIGERANT LINES Condensing units have provisions for flare connections Pressure taps are provided on the service valves of outdoor unit for compressor suction and liquid pressures The indoor end of the recommended refrigerant line sets may...

Page 3: ...into either valve pressure tap port thru the tubing and out the other port while brazing 8 Braze using accepted good brazing techniques LEAK CHECK IMPORTANT Replace pressure tap port valve core before attaching hoses for evacuation After the brazing operation of refrigerant lines to both the outdoor and indoor unit is completed the field brazed connections must be checked for leaks Pressurize thro...

Page 4: ...fy connections between the outdoor unit the thermostat and the indoor unit Table 1 NEC Class II Control Wiring 24 VOLTS WIRE SIZE MAX WIRE LENGTH 18 AWG 150 FT 16 AWG 225 FT 14 AWG 300 FT 8 Table 1 defines maximum total length of low voltage wiring from outdoor unit to indoor unit and to thermostat 9 Mount the indoor thermostat in accordance with instruc tion included with the thermostat Wire per ...

Page 5: ...ordance with procedures found in the Service Facts J ELECTRIC HEATERS Electric heaters if used are to be installed in the air han dling device according to the instructions accompanying the air handler and the heaters K OUTDOOR THERMOSTAT An outdoor thermostat TAYSTAT250B may be field installed For data see wiring diagram attached to unit and instruction sheet packaged with outdoor thermostat L SE...

Page 6: ... 4 181 7 1 8 44 1 3 4 457 18 2TWB0018AA 2 2 651 25 5 8 724 28 1 2 651 25 5 8 3 4 5 16 127 5 57 2 1 4 181 7 1 8 44 1 3 4 457 18 2TWB0024AA 2 2 730 28 3 4 724 28 1 2 651 25 5 8 3 4 5 16 137 5 3 4 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2TWB0030AA 2 2 730 28 3 4 724 28 1 2 651 25 5 8 7 8 3 8 137 5 3 4 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2TWB0036AA 3 2 832 32 3 4 829 32 5 8 756 29 3 4 7 8 3 8 137 5 3 4 86 3...

Page 7: ...18 BC52D5 5 7 Installer s Guide MOUNTING HOLE LOCATION Note All dimensions are in MM Inches NOTE For model base size see table on page 6 From Dwg 21D152989 Rev 0 ...

Page 8: ...RICAL Compressor O D Fan Won t Start Compressor Will Not Start But O D Fan Runs O D Fan Won t Start Compressor Hums But Won t Start Compressor Cycles on IOL I D Blower Won t Start DEFROST Unit Won t Initiate Defrost Defrost Terminates on Time Unit Icing Up W H A T T O C H E C K M O D E P O W E R S U P P L Y H I G H V O L T A G E W I R I N G C O M P R E S S O R I O L R U N C A P A C I T O R S T A R...

Reviews: