background image

18-BC52D5-5

3

Installer’s Guide

a. When the refrigerant lines have to be fastened to floor

joists or other framing in a structure, use isolation
type hangers.

b. Isolation hangers should also be used when refriger-

ant lines are run in stud spaces or enclosed ceilings.

c. Where the refrigerant lines run through a wall or sill,

they should be insulated and isolated.

d. Isolate the lines from all ductwork.

E. SERVICE VALVE OPERATION

BRASS LIQUID AND GAS LINE SERVICE VALVES

The Brass Liquid and Gas Line Service Valves are factory
shipped in the seated position to hold factory charge. The
pressure tap service port (when depressed) opens only to the
field brazing side of the valve when the valve is in the seated
position. The liquid line valve is 

not 

a back seating valve (see

WARNING 

below).

WARNING

!

Extreme caution should be exercised when opening the
Liquid and Gas Line Service Valves. Turn valve stem
counterclockwise only until the stem contacts the rolled
edge. (See Figures 4 and 5) No torque is required.

BRAZING REFRIGERANT LINES

1. Remove lower access cover to access service valves.

2. Before brazing, remove plugs from external copper stub

tubes. Clean internal and external surfaces of stub tubes
prior to brazing.

3. Cut and fit tubing, minimizing the use of sharp 90° bends.

4. Insulate the entire gas line and its fittings.

5. Do 

NOT

 allow uninsulated liquid line to come in direct

contact with bare gas line.

6.

Precautions should be taken to avoid heat damage
to the pressure tap valve core during brazing. It is
recommended that the pressure tap port valve
core be removed and a wet rag wrapped around
the valve body.

NOTICE:
Use care to make sure that no moisture enters pressure tap
port, while wet rag is being used.

NOTICE:
Precautions should be taken to avoid heat damage to
basepan during brazing. It is recommended to keep the
flame directly off of the basepan.

7. Use a Dry Nitrogen Purge and Brazing Alloy without

flux when brazing the field line to the copper factory
connection. Flow dry nitrogen into either valve pressure
tap port, thru the tubing and out the other port while
brazing.

8. Braze using accepted good brazing techniques.

LEAK CHECK

IMPORTANT

:

Replace pressure tap port valve core before attaching hoses for
evacuation.

After the brazing operation of refrigerant lines to both the
outdoor and indoor unit is completed, the field brazed
connections must be checked for leaks. Pressurize through
the service valve ports, the indoor unit and field refrigerant
lines with dry nitrogen to 350-400 psi. Use soap bubbles or
other leak-checking methods to see that all field joints are
leak-free! If not, 

release pressure

; then repair!

SYSTEM EVACUATION

NOTE:
Since the outdoor unit has a refrigerant charge, the gas and
liquid line valves must remain closed.

1. Upon completion of leak check, evacuate the refrigerant

lines and indoor coil before opening the gas and liquid
line valves.

2. Attach appropriate hoses from manifold gauge to gas

and liquid line pressure taps.

NOTE:
Unnecessary switching of hoses can be avoided and com-
plete evacuation of all lines leading to sealed system can
be accomplished with manifold center hose and connecting
branch hose to a cylinder of HCFC-22 and vacuum pump.

3. Attach center hose of manifold gauges to vacuum pump.

4. Evacuate until the micron gauge reads no higher than

350 microns.

5. Close off valve to vacuum pump and observe the micron

gauge. If gauge pressure rises above 500 microns in one
(1) minute, then evacuation is incomplete or system has
a leak.

6. If vacuum gauge does not rise above 500 microns in

one (1) minute, the evacuation should be complete.

7. With vacuum pump and micron gauge blanked off, open

valve on HCFC-22 cylinder and charge refrigerant lines
and indoor coil with vapor to tank pressure of HCFC-22
supply.

NOTE:
DO NOT VENT REFRIGERANT INTO THE ATMOSPHERE.

8. Close valve on HCFC-22 supply cylinder. Close valves on

manifold gauge set and remove refrigerant charging
hoses from liquid and gas pressure tap ports.

NOTE:
A 3/16" Allen wrench is required to open liquid line service
valve. A 1/4" Open End or Adjustable wrench is required to
open gas line valve. A 3/4" Open End wrench is required to
take off the valve stem cap.

 GAS LINE SERVICE VALVE

5

Summary of Contents for 2TWB0012-036AA

Page 1: ...rise which are not covered sufficiently for the purchaser s purposes the matter should be referred to your installing dealer or local distributor A GENERAL The following instructions cover 2TWB0012 036AA Heat Pump Units NOTE These outdoor units may be used with indoor units equipped with Thermostatic Expansion Valve or Accutron Flow Control Check Valve F C C V assembly for refrigerant flow control...

Page 2: ...el in an envelope attached to the outdoor unit Outdoor unit nameplate will have correct orifice size specified as BAYFCCV A for rated performance D INSTALLING REFRIGERANT LINES Condensing units have provisions for flare connections Pressure taps are provided on the service valves of outdoor unit for compressor suction and liquid pressures The indoor end of the recommended refrigerant line sets may...

Page 3: ...into either valve pressure tap port thru the tubing and out the other port while brazing 8 Braze using accepted good brazing techniques LEAK CHECK IMPORTANT Replace pressure tap port valve core before attaching hoses for evacuation After the brazing operation of refrigerant lines to both the outdoor and indoor unit is completed the field brazed connections must be checked for leaks Pressurize thro...

Page 4: ...fy connections between the outdoor unit the thermostat and the indoor unit Table 1 NEC Class II Control Wiring 24 VOLTS WIRE SIZE MAX WIRE LENGTH 18 AWG 150 FT 16 AWG 225 FT 14 AWG 300 FT 8 Table 1 defines maximum total length of low voltage wiring from outdoor unit to indoor unit and to thermostat 9 Mount the indoor thermostat in accordance with instruc tion included with the thermostat Wire per ...

Page 5: ...ordance with procedures found in the Service Facts J ELECTRIC HEATERS Electric heaters if used are to be installed in the air han dling device according to the instructions accompanying the air handler and the heaters K OUTDOOR THERMOSTAT An outdoor thermostat TAYSTAT250B may be field installed For data see wiring diagram attached to unit and instruction sheet packaged with outdoor thermostat L SE...

Page 6: ... 4 181 7 1 8 44 1 3 4 457 18 2TWB0018AA 2 2 651 25 5 8 724 28 1 2 651 25 5 8 3 4 5 16 127 5 57 2 1 4 181 7 1 8 44 1 3 4 457 18 2TWB0024AA 2 2 730 28 3 4 724 28 1 2 651 25 5 8 3 4 5 16 137 5 3 4 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2TWB0030AA 2 2 730 28 3 4 724 28 1 2 651 25 5 8 7 8 3 8 137 5 3 4 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2TWB0036AA 3 2 832 32 3 4 829 32 5 8 756 29 3 4 7 8 3 8 137 5 3 4 86 3...

Page 7: ...18 BC52D5 5 7 Installer s Guide MOUNTING HOLE LOCATION Note All dimensions are in MM Inches NOTE For model base size see table on page 6 From Dwg 21D152989 Rev 0 ...

Page 8: ...RICAL Compressor O D Fan Won t Start Compressor Will Not Start But O D Fan Runs O D Fan Won t Start Compressor Hums But Won t Start Compressor Cycles on IOL I D Blower Won t Start DEFROST Unit Won t Initiate Defrost Defrost Terminates on Time Unit Icing Up W H A T T O C H E C K M O D E P O W E R S U P P L Y H I G H V O L T A G E W I R I N G C O M P R E S S O R I O L R U N C A P A C I T O R S T A R...

Reviews: