background image

18-AD43D1-1A-EN  

3

Installer’s Guide

IMPORTANT:  

Do not unseal refrigerant tubing until ready to fit refrigerant 

lines.

There is only a holding charge of dry air in the indoor coil, therefore 
no loss of operating refrigerant charge occurs when the sealing 
plugs are removed.

F. INSTALLING / BRAZING REFRIGERANT LINES

Do NOT open refrigerant valve at the outdoor unit until the 

refrigerant lines and coil have been brazed, evacuated, and 

leak checked. This would cause contamination of the refriger-

ant or possible discharge of refrigerant to the atmosphere.

1.  The following steps are to be considered when installing 

the refrigerant lines:

a. Determine the most practical way to run the lines.
b. Consider types of bends to be made and space 

limitations.

    c. Route the tubing making all required bends and 

        properly secure the tubing before making final 

        connections.

NOTE:

 Refrigerant lines must be isolated from the structure and 

the holes must be sealed weather tight after installation.

NOTE:   

The TXV setting on this unit may run high superheat  

(15-25°F) by design when measured at the outdoor unit.

Figure 4

Note: When installing coil onto an S-Series furnaces 

in horizontal right or downflow configuration, bend 

the flanges downward for a flush fit.

CAUTION

!

NOTE:  

TXV bulb MUST be protected (wrapped with wet rag) or 

removed, while brazing the tubing. Overheating of the 

sensing bulb will affect the functional characteristics and 

performance of the comfort coil.

When replacing the TXV bulb, reinstall the bulb in the 

proper orientation. 

9.        Wrap  the  TXV  with  insulation  after  the  spring  clip  has  been                                                                                                                                             
        installed.

G.  LEAK CHECK

1.  Using a manifold gauge, connect an external supply of dry 

nitrogen to the gauge port on the liquid line.  

2.  Pressurize the connecting lines and indoor coil to 150 PSIG 

maximum.

3.  Leak check brazed line connections using soap bubbles.

Repair leaks (if any) after relieving pressure.

4.  Evacuate and charge the system per the instructions packaged 

with the outdoor unit.

Figure 5

Capillary tubes will come 

out the top of bulb when 

positioned correctly.

PAINTED AREAS OF THE UNIT MUST BE SHIELDED DURING 

BRAZING.

1.  Remove both rubber plugs from the indoor coil.
2.  Field supplied tubing should be cut square, round and free 

of burrs at the connecting end. Clean the tubing to prevent 
contaminants from entering the system.

3.  Run the refrigerant tubing into the stub tube sockets of the 

indoor unit coil. 

4.  Flow a small amount of nitrogen through the tubing while 

brazing.

5.  Use good brazing technique to make leakproof joints.
6.  Minimize the use of sharp 90 degree bends.
7.  Insulate the suction line and its fittings.
8.  Do NOT allow un-insulated lines to come into contact with 

each other.

Summary of Contents for 4PXCBU36BS3HAC

Page 1: ...pping into the supply ductwork NOTE 4PXC upflow coils may be installed in Upflow Down flow Horizontal Right with kit and Horizontal Left with kit 1 FURNACE AND COIL The coil MUST BE installed downstre...

Page 2: ...lling the coil in the horizontal position you MUST use the horizontal kit listed below for this coil model num ber and follow the instructions in the installation guide provided with the conversion ki...

Page 3: ...TION NOTE TXV bulb MUST be protected wrapped with wet rag or removed while brazing the tubing Overheating of the sensing bulb will affect the functional characteristics and performance of the comfort...

Page 4: ...g careful to prevent fin damage Use chemical cleaners only when necessary H CONDENSATE DRAIN PIPING Condensate drain connections are located in the drain pan at the bottom of the coil enclosure assemb...

Page 5: ...ONTROL HEIGHT A IN 22 1 2 OVERALL WIDTH B IN 17 1 2 OPENING WIDTH C IN 16 5 8 TOP OPENING D 15 3 4 GAS CONNECTION LIQUID CONNECTION MATCHED FURNACE WIDTH NO ADAPTER RQUIRED 17 1 2 DRAIN PAN PLASTIC TX...

Page 6: ...NO Is superheat 25F YES NO Is indoor temperature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is co...

Page 7: ...18 AD43D1 1A EN 7 Installer s Guide...

Page 8: ...idential applications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change de...

Reviews: