background image

 18-AD43D1-1A-EN

Installer’s Guide

Figure 6

I.  CLEANING THE COIL

The two piece door allows removal of the outer casing doors 
without interference from refrigerant or condensate lines.

The foil covered insulation on 4PXC coils should be wiped down 
and residual dirt and dust should be vacuumed up to maintain 
good air quality. See Figure 6.

The manufacturer’s recommendation for coil cleaning is to initially 
use only water to wash away debris that may have collected on 
and in the coil fin surface. Removing an evaporator coil is the best 
way to effectively clean a coil that is heavily contaminated. This 
is accomplished by removing the coil from the cabinet, sealing 
the liquid and vapor line and using a strong water stream such 
as from a garden hose, being careful to prevent fin damage. Use 
chemical cleaners, only when necessary.  

H.  CONDENSATE DRAIN PIPING

Condensate drain connections are located in the drain pan at 
the bottom of the coil/enclosure assembly. The female threaded 
fitting protrudes outside of the enclosure for external connection.  
A field fabricated trap is not required for proper drainage due to 
the positive pressure of the furnace; however, it is recommended 
to prevent efficiency loss of conditioned air. 
1.  The drain hole in the drain pan must be cleared of all insulation.
2.  Insulate the primary drain line to prevent sweating where 

dew point temperatures may be met. (Optional depending on 
climate and application needs)  

3.  Connect the secondary drain line to a separate drain line (no 

trap is needed in this line).  

NOTE:   

Refer to Service Guideline, UN-SVG001C-EN, Evaporator 

Coil Cleaning and Condensate Drain Maintenance Guide-

lines for important information on cleaning coils with 

chemical treatments.

Summary of Contents for 4PXCBU36BS3HAC

Page 1: ...pping into the supply ductwork NOTE 4PXC upflow coils may be installed in Upflow Down flow Horizontal Right with kit and Horizontal Left with kit 1 FURNACE AND COIL The coil MUST BE installed downstre...

Page 2: ...lling the coil in the horizontal position you MUST use the horizontal kit listed below for this coil model num ber and follow the instructions in the installation guide provided with the conversion ki...

Page 3: ...TION NOTE TXV bulb MUST be protected wrapped with wet rag or removed while brazing the tubing Overheating of the sensing bulb will affect the functional characteristics and performance of the comfort...

Page 4: ...g careful to prevent fin damage Use chemical cleaners only when necessary H CONDENSATE DRAIN PIPING Condensate drain connections are located in the drain pan at the bottom of the coil enclosure assemb...

Page 5: ...ONTROL HEIGHT A IN 22 1 2 OVERALL WIDTH B IN 17 1 2 OPENING WIDTH C IN 16 5 8 TOP OPENING D 15 3 4 GAS CONNECTION LIQUID CONNECTION MATCHED FURNACE WIDTH NO ADAPTER RQUIRED 17 1 2 DRAIN PAN PLASTIC TX...

Page 6: ...NO Is superheat 25F YES NO Is indoor temperature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is co...

Page 7: ...18 AD43D1 1A EN 7 Installer s Guide...

Page 8: ...idential applications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change de...

Reviews: