background image

 18-AD43D1-1A-EN

Installer’s Guide

Is sub cooling at the

outdoor unit between

8 to 12F?

Troubleshooting Indoor TXV / Cooling Mode

NO

YES

Is superheat

< 5F?

YES

Correct air

flow

problem

Is air flow at least

350 CFM per ton?

YES

NO

Remove sensing bulb from the

suction line. Measure superheat

at indoor coil while holding the

bulb in bare hand for one minute.

Does superheat decrease?

Measure superheat at indoor coil

while placing the bulb in an ice

and water bath for one minute.

Does superheat increase?

YES

Replace the

TXV

TXV is OK

NO

Is superheat

< 25F?

YES

NO

Is indoor

temperature more

than 85F?

NO

Is sub cooling less

than 8F?

YES

Confirm that charge

is correct and look

for dirty or restricted

outdoor coil.

Confirm that

charge is

correct.

NO

Before starting

, insure the

blower wheel, indoor and outdoor

coils are clean.

Is the liquid line

temperature at indoor

coil within 8F of outdoor

liquid line temperature?

YES

Verify line set is

sized properly

for application

NO

The system is running at max

capacity and this may be

causing the High superheat.

Wait until indoor temperature

is less than 80F and check

superheat again.

YES

YES

Verify Inlet screen

of inlet tube

assembly is clear

of debris

NO

Verify Inlet screen

of inlet tube

assembly is clear

of debris

NO

Summary of Contents for 4PXCBU36BS3HAC

Page 1: ...pping into the supply ductwork NOTE 4PXC upflow coils may be installed in Upflow Down flow Horizontal Right with kit and Horizontal Left with kit 1 FURNACE AND COIL The coil MUST BE installed downstre...

Page 2: ...lling the coil in the horizontal position you MUST use the horizontal kit listed below for this coil model num ber and follow the instructions in the installation guide provided with the conversion ki...

Page 3: ...TION NOTE TXV bulb MUST be protected wrapped with wet rag or removed while brazing the tubing Overheating of the sensing bulb will affect the functional characteristics and performance of the comfort...

Page 4: ...g careful to prevent fin damage Use chemical cleaners only when necessary H CONDENSATE DRAIN PIPING Condensate drain connections are located in the drain pan at the bottom of the coil enclosure assemb...

Page 5: ...ONTROL HEIGHT A IN 22 1 2 OVERALL WIDTH B IN 17 1 2 OPENING WIDTH C IN 16 5 8 TOP OPENING D 15 3 4 GAS CONNECTION LIQUID CONNECTION MATCHED FURNACE WIDTH NO ADAPTER RQUIRED 17 1 2 DRAIN PAN PLASTIC TX...

Page 6: ...NO Is superheat 25F YES NO Is indoor temperature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is co...

Page 7: ...18 AD43D1 1A EN 7 Installer s Guide...

Page 8: ...idential applications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change de...

Reviews: