background image

Table of Contents

General ............................................................................... 1

Application Information ................................................ 1

Recommendation ............................................................. 2

Furnace in Upflow Position .......................................... 2

Furnace in Downflow Position ..................................... 2

Furnace in Horizontal Right Position ........................ 3

Furnace in Horizontal Left Position ........................... 4

Maximum Airflow Setting, CFM ................................... 5

Installing / Brazing Refrigerant Lines ....................... 5

Leak Check........................................................................ 6

Condensate Drain Piping .............................................. 6

Cleaning the Coil ............................................................. 6

Outline Drawings ............................................................ 7

Troubleshooting Indoor TXV / Cooling Mode ......... 10

Installer’s Guide

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — 

This Document is 

customer property

 and is to remain with this unit.  Please return to service informa-

tion pack upon completion of work.

WARNING

!

WARNING (Medium/high pressure) 

Contains Refrigerant!
System contains oil and refrigerant under high pressure.  
Recover refrigerant to relieve  pressure before opening the 
system.  See unit nameplate for refrigerant type.  Do not 
use non-approved refrigerants, refrigerant substitutes, or 
refrigerant additives.
Failure to follow proper procedures or the use of non-
approved refrigerants, substitutes, or refrigerant additives 
could result in death, serious injury, or equipment damage.

A341869P33

IMPORTANT: Review your installation requirements.  Check 
the table on the outline drawings and note all dimensions 
for your coil before beginning the installation.

Figure 1

18-AD35D1-2D-EN

Cased Aluminum "Convertible" Coils

Models:
4TXCA002DS3HCA
4TXCA032DS3HCA
4TXCB003DS3HCA
4TXCB004DS3HCA
4TXCB006DS3HCA

4TXCC005DS3HCA
4TXCC007DS3HCA
4TXCD008DS3HCA
4TXCC009DS3HCA
4TXCD010DS3HCA

NOTE: 

OPTIONAL DOWNFLOW GASKET INSTALLATION: For 

unusually humid applications that expect prolonged 

operation above 70% RH, it is recommended to use the 

BAYGSKT001A0 gasket kit to prevent water from forming 

on the bottom of the drain pan and dripping into the sup-

ply ductwork.

WARNING

!

This product can expose you to chemicals including lead, which 
are known to the State of California to case cancer and birth defects 
or other reproductive harm. For more information go to www. 
P65Warnings.ca.gov

A.  GENERAL

These coils are designed for use in combination with a heat pump 
or cooling outdoor section using 

R-410A REFRIGERANT

The 4TXC equipment has been evaluated in accordance with 
the Code of Federal Regulations, Chapter XX, Part 3280 or the 
equivalent. “Suitable for Mobile Home use” The height of the 
Furnace, Coil and discharge duct work must be 7 ft. or less.
Inspect the coil for shipping damage.  Notify the transporta-
tion company immediately if the coil is damaged.

B.  APPLICATION INFORMATION

1. FURNACE AND COIL
The coil MUST BE installed downstream (in the outlet air) 
of the furnace.  
2. INDOOR UNIT AIRFLOW
Indoor unit must provide the required airflow for the heat 
pump or cooling combinations approved for these coils.

Summary of Contents for 4TXCA002DS3HCA

Page 1: ...oil before beginning the installation Figure 1 18 AD35D1 2D EN Cased Aluminum Convertible Coils Models 4TXCA002DS3HCA 4TXCA032DS3HCA 4TXCB003DS3HCA 4TXCB004DS3HCA 4TXCB006DS3HCA 4TXCC005DS3HCA 4TXCC00...

Page 2: ...ency a Remove the coil by sliding the coil out of the coil enclo sure b Optional but recommended Remove the factory in stalled two piece baffle assembly from the top of the coil by removing the 5 16 h...

Page 3: ...mmended On 4TXCC009DS and 4TXCD010DS only remove the 2 outer water diverter baffles by removing the 5 16 hex head screws See Fig ure 6 IMPORTANT The 4TXC cased coil must be placed downstream of the fu...

Page 4: ...condensing downflow hori zontal and upflow horizontal furnaces may only be rotated onto their left side Connection brackets for coil furnace alignment are included with the furnaces a In horizontal le...

Page 5: ...rubber plugs from the indoor coil 2 Field supplied tubing should be cut square round and free of burrs at the connecting end Clean the tubing to prevent contaminants from entering the system 3 Run th...

Page 6: ...for proper drainage due to the positive pressure of the furnace however it is recommended to prevent efficiency loss of conditioned air 1 The drain hole in the drain pan must be cleared of all insula...

Page 7: ...ALL WIDTH B IN 14 1 2 14 1 2 17 1 2 21 17 1 2 21 21 OPENING WIDTH C IN 13 5 8 13 5 8 16 5 8 20 1 8 16 5 8 20 1 8 20 1 8 TOP OPENING D 12 3 4 12 3 4 15 3 4 19 1 4 15 3 4 19 1 4 19 1 4 GAS CONNECTION 3...

Page 8: ...T LBS 50 REFRIGERANT CONTROL TXV NON BLEED HEIGHT A IN 17 1 2 OVERALL WIDTH B IN 17 1 2 OPENING WIDTH C IN 16 5 8 TOP OPENING D 15 3 4 GAS CONNECTION 3 4 LIQUID CONNECTION 3 8 MATCHED FURNACE WIDTH NO...

Page 9: ...EED HEIGHT A IN 26 7 8 30 11 16 OVERALL WIDTH B IN 24 1 2 24 1 2 OPENING WIDTH C IN 23 5 8 23 5 8 TOP OPENING D 22 3 4 22 3 4 GAS CONNECTION 7 8 LIQUID CONNECTION 3 8 MATCHED FURNACE WIDTH NO ADAPTER...

Page 10: ...NO Is superheat 25F YES NO Is indoor temperature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is c...

Page 11: ...18 AD35D1 2D EN 11 Installer s Guide...

Page 12: ...icy of continuous product and product data improvement it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 For more information contact you...

Reviews: