Installer’s Guide

C.  RECOMMENDATION

If a coil is part of the total system installation, use the In-
staller’s Guide packaged with the furnaces, outdoor sections, 
and thermostat for physically installing those components.

CAUTION

!

Caution: This coil is pressurized with 8-12 psig of dry air. 

Do not stand directly in front of the coil connections when 

removing sealing plugs.  If no pressure is released, check 

for leaks.  

 

D.  FURNACE IN UPFLOW POSITION 

1.  UPFLOW COIL CONVERSION: While not required, 

optional removal of some coil components will maximize 

airflow efficiency.

 

a.  Remove the coil by sliding the coil out of the coil 

enclosure.

 

b.  Optional but recommended: Remove the factory in-

stalled two-piece baffle assembly from the top of the coil 

by removing the 5/16” hex head screws.  See Figure 2.  

Replace only the top baffle using the same screws previ-

ously provided.

 

c.  Optional but recommended: On 4TXCC009DS and 

4TXCD010DS only, remove the (2) outer water diverter 

baffles by removing the 5/16” hex head screws.  See Figure 5.  

 

d.  Optional for maximum efficiency: Remove the horizon-

tal drain pan from the coil and discard.

2.  UPFLOW GAS FURNACE 

 

a.  Apply gasket material (duct seal field supplied) to ALL 

mating surfaces between the furnace and the coil case.

 

b.  Set the coil case on top of the furnace.  Connect the duct-

work to the coil case using field supplied screws.

 

c.  Secure the coil case to the furnace and seal for air leaks 

as required.

FOR UPFLOW / 

HORIZONTAL LEFT 

INSTALLATIONS

E.  FURNACE IN DOWNFLOW POSITION

1.  DOWNFLOW COIL CONVERSION: While not required, 

optional removal of some coil components will maximize 

airflow efficiency.

 

a.  Remove the coil by sliding the coil out of the coil enclo-

sure.

 

b.  Optional but recommended: Remove the factory in-

stalled two-piece baffle assembly from the top of the coil 

by removing the 5/16” hex head screws.  See Figure 2.  

Replace only the top baffle using the same screws previ-

ously provided.

 

c.  Optional for maximum efficiency: Remove the 

horizontal drain pan from the coil and discard.

2.  DOWNFLOW GASKET INSTALLATION (OPTIONAL): 

For unusually humid applications that expect prolonged 

operation above 70% RH, it is recommended to use the 

BAYGSKT001A0 gasket kit to prevent water from form-

ing on the bottom of the drain pan and dripping into the 

supply ductwork.

 

a.  Lay the coil on its back side.

 

b.  Locate the 4" wide gasket material found in 

BAYGSKT001A0.

 

c.  Attach the 4" gasket material to three sides of the 

bottom of the drain pan as shown. Make sure to start 

by matching up the edge of the gasket material to the 

inner edge of the drain pan by the coil fins and working 

outwards.

 

d.  The gasket material can be cut or ripped easily so 

that it can be tailored to fit. The gasket material must 

cover the three sides along the entire length of the coil as 

shown in Figure 4.

Figure 3

Figure 2

Remove
and 
Discard

Replace

UPFLO

W

FURNA

CE

CASED

COIL

SCREWS

(BOTH SIDES)

STANDOFFS

(BOTH SIDES)

STANDOFFS (4)

DRILL SCREWS (4)

Figure 4

Attach Downflow 
Bottom Gasket

Start 
here

3.  DOWNFLOW GAS FURNACE 
When a coil is used with a downflow furnace, a subbase is not 

required between the coil case and combustible flooring.  

 

a.  Place the coil case on the furnace  supply air plenum.

 

b.  Secure the coil case to the plenum. 

 

c.  Set the furnace on top of the coil case, making sure that 

the back side of the discharge opening is snug up against the 

duct flange at the top rear of the coil case.

 

d.  Secure the coil case to the furnace and seal for air leaks as 

required.

Summary of Contents for 4TXCA002DS3HCA

Page 1: ...oil before beginning the installation Figure 1 18 AD35D1 2D EN Cased Aluminum Convertible Coils Models 4TXCA002DS3HCA 4TXCA032DS3HCA 4TXCB003DS3HCA 4TXCB004DS3HCA 4TXCB006DS3HCA 4TXCC005DS3HCA 4TXCC00...

Page 2: ...ency a Remove the coil by sliding the coil out of the coil enclo sure b Optional but recommended Remove the factory in stalled two piece baffle assembly from the top of the coil by removing the 5 16 h...

Page 3: ...mmended On 4TXCC009DS and 4TXCD010DS only remove the 2 outer water diverter baffles by removing the 5 16 hex head screws See Fig ure 6 IMPORTANT The 4TXC cased coil must be placed downstream of the fu...

Page 4: ...condensing downflow hori zontal and upflow horizontal furnaces may only be rotated onto their left side Connection brackets for coil furnace alignment are included with the furnaces a In horizontal le...

Page 5: ...rubber plugs from the indoor coil 2 Field supplied tubing should be cut square round and free of burrs at the connecting end Clean the tubing to prevent contaminants from entering the system 3 Run th...

Page 6: ...for proper drainage due to the positive pressure of the furnace however it is recommended to prevent efficiency loss of conditioned air 1 The drain hole in the drain pan must be cleared of all insula...

Page 7: ...ALL WIDTH B IN 14 1 2 14 1 2 17 1 2 21 17 1 2 21 21 OPENING WIDTH C IN 13 5 8 13 5 8 16 5 8 20 1 8 16 5 8 20 1 8 20 1 8 TOP OPENING D 12 3 4 12 3 4 15 3 4 19 1 4 15 3 4 19 1 4 19 1 4 GAS CONNECTION 3...

Page 8: ...T LBS 50 REFRIGERANT CONTROL TXV NON BLEED HEIGHT A IN 17 1 2 OVERALL WIDTH B IN 17 1 2 OPENING WIDTH C IN 16 5 8 TOP OPENING D 15 3 4 GAS CONNECTION 3 4 LIQUID CONNECTION 3 8 MATCHED FURNACE WIDTH NO...

Page 9: ...EED HEIGHT A IN 26 7 8 30 11 16 OVERALL WIDTH B IN 24 1 2 24 1 2 OPENING WIDTH C IN 23 5 8 23 5 8 TOP OPENING D 22 3 4 22 3 4 GAS CONNECTION 7 8 LIQUID CONNECTION 3 8 MATCHED FURNACE WIDTH NO ADAPTER...

Page 10: ...NO Is superheat 25F YES NO Is indoor temperature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is c...

Page 11: ...18 AD35D1 2D EN 11 Installer s Guide...

Page 12: ...icy of continuous product and product data improvement it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 For more information contact you...

Reviews: