background image

Installer’s Guide

18-CD21D1-12

   9. Using a leak detection solution or soap suds, check 

for leaks at the pressure outlet boss and pressure 
tap test screw.

   10.  Turn on system power and check operation of the 

unit.

CAUTION

!

Replace and/ or tighten all plugs removed or loosened 

when adjusting gas pressure. Leak check the fittings 

before placing the furnace into regular service.

Failure to follow this warning could result in fire, explo-

sion, or property damage.

Table 10 lists the main burner orifices shipped with 
the furnace.  If a change of orifices is required to cor-
rect the input rate, refer to Table 11.

TABLE 9

NATURAL GAS ONLY

TABLE OF CUBIC FEET PER HOUR OF GASFOR VARIOUS PIPE 

SIZES AND LENGTHS

PIPE-

SIZE

LENGTH OF PIPE

10

20

30

40

50

60

70

1/2

132

92

73

63

56

50

46

3/4

278

190

152

130

115

105

96

1

520

350

285

245

215

195

180

1-1/4

1050

730

590

520

440

400

370

  This table is based on pressure drop of 0.3 inch W.C. and 0.6 SP.GR. gas

TABLE 10

ORIFICE SIZES

INPUT

RATING

BTUH

NUMBER

OF

BURNERS

MAIN BURNER ORIFICE

DRILL SIZE

NAT. GAS

LP GAS

40,000
60,000
80,000

100,000
120,000
140,000

2
3
4
5
6
7

45
45
45
45
45
45

56
56
56
56
56
56

TABLE 11

PART NUMBERS FOR REPLACEMENT ORIFICES

DRILL

SIZE

PART

NUMBER

DRILL

SIZE

PART

NUMBER

44
45
46
47
48
49 
50

ORF00501
ORF00644
ORF00909
ORF00910
ORF01099
ORF00503 
ORF00493

54
55
56
57
58
59

ORF00555
ORF00693
ORF00907
ORF00908
ORF01338
ORF01339

HIGH ALTITUDE DERATE

Input  ratings  (BTUH)  of  these  furnaces  are  based  on 

sea level operation and should not be changed at eleva-
tions up to 2,000 ft.
If the installation is 2,000 ft. or above, the furnace in-

put  rate  (BTUH)  shall  be  reduced  4%  for  each  1,000 

ft. above sea level. The furnace input rate shall be 
checked by clocking the gas flow rate (CFH) and mul-
tiplying by the heating value obtained from the local 
utility supplier for the gas being delivered at the in-
stalled altitude.  Input rate changes can be made by 
adjusting the manifold pressure (min 3.0 - max 3.7 in. 
W.C. - Natural Gas) or changing orifices (orifice change 
may not always be required). If the desired input rate 
cannot be achieved with a change in manifold pressure, 
then the orifices must be changed. LP installations will 
require an orifice change.
Installation of this furnace at altitudes above 2,000 ft. 
(610m) shall be in accordance with local codes, the 

Na-

tional Fuel Gas Code, ANSI Z223.1/ NFPA 54 or Na-
tional Standard of Canada, Natural Gas and Propane 
Installation Code, CSA B149.1.

 Installation of this fur-

nace at altitudes above 2,000 ft. (610m) shall be made 
in accordance with the listed high Altitude Conversion 

Kit available with this furnace.

IMPORTANT:

Re-install the propane orifices to the same depth as the 

orifices supplied with the equipment.

 
See Table 14 for help in selecting orifices if orifice 
change is required. Furnace input rate and tempera-
ture rise should be checked again after changing ori-
fices to confirm the proper rate for the altitude.
Installations above 4,000 feet may require a pressure 

switch change.  If required, use the BAYHALT*** Kit 
(High  Altitude  Accessory  Kit)  listed  in  PRODUCT 

DATA.

WARNING

!

 

EXPLOSION HAZARD!
PROPANE GAS IS HEAVIER THAN AIR AND MAY 
COLLECT IN ANY LOW AREAS OR CONFINED SPAC-
ES. IN ADDITION, ODORANT FADE MAY MAKE THE 
GAS UNDETECTABLE EXCEPT WITH A WARNING 
DEVICE.  IF THE GAS FURNACE IS INSTALLED IN A 
BASEMENT, AN EXCAVATED AREA OR A CONFINED 
SPACE, IT IS STRONGLY RECOMMENDED TO CON-
TACT A GAS SUPPLIER TO INSTALL A GAS DETECT-
ING WARNING DEVICE IN CASE OF A GAS LEAK

NOTE:

  The manufacturer of your furnace does NOT test 

any detectors and makes no representations regarding 

any brand or type of detector.

FINAL MANIFOLD PRESSURE SET-

TINGS (inches w.c.)

FUEL

PRESSURE

NATURAL GAS

3.5" W.C.

LP GAS

10.5" W.C.

TABLE 12

Summary of Contents for ADD1B060A9H31B

Page 1: ...with this unit Please return to service information pack upon completion of work Installer s Guide UD1B100A9H31B UD1B100G9H31A UD1C100A9H51B UD1C100G9H51A UD1D120A9H51B UD1D120G9H51A UD1D140A9H51B UD1...

Page 2: ...ate mark ing e 100 of the furnace combustion air requirement must come from outside the structure SAFETY SECTION CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each ap...

Page 3: ...ty signal words are used to designate a degree or level of seriousness associated with a particular hazard The signal words for safety markings are WARNING and CAUTION a WARNING indicates a potentiall...

Page 4: ...avoid physical damage from vehicles GENERAL INSTALLATION INSTRUCTIONS The manufacturer assumes no responsibility for equip ment installed in violation of any code or regulation It is recommended that...

Page 5: ...D TUD1A040A9H21B TUD1A040G9H21A 14 1 2 9 5 8 13 1 4 13 TUD1B060A9H31B TUD1B060G9H31A TUD1B080A9H31B TUD1B080G9H31A TUD1B100A9H31B TUD1B100G9H31A 17 1 2 9 5 8 16 1 4 16 TUD1C080A9H41B TUD1C080G9H41A T...

Page 6: ...6 18 CD21D1 12 Installer s Guide From Dwg 21C341700 Sh 1 Rev 0 DD1 HF OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES...

Page 7: ...coil in the horizontal posi tion See Figure 4 IMPORTANT The 2 4TXC cased coil must be placed downstream of the furnace In horizontal installations the apex of the coil may point either toward or away...

Page 8: ...ir open ings provided in the furnace casing must be kept free of obstructions which restrict the flow of air Airflow restrictions affect the efficiency and safe operation of the furnace Keep this in m...

Page 9: ...rcial buildings Buildings with indoor pools Furnaces installed in commercial laundry rooms Furnaces installed in hobby or craft rooms Furnaces installed near chemical storage areas Exposure to the fol...

Page 10: ...the space containing the furnace Minimum return air entering temperature for the furnace is 55 F Where there is no complete return duct system the re turn connection must be run full size from the fur...

Page 11: ...Thin cloths should be placed over the registers and the furnace fan should be run for 10 minutes Don t forget to remove the cloths be fore you start the furnace FILTER REMOVE FILTER FROM UPFLOW FURNAC...

Page 12: ...ACK960 The following checklist should be used when installing a right or left side return filter on an upflow furnace a Remove the filter b Leave the bottom panel in place c Make side cutout by follow...

Page 13: ...stream of the fur nace See Figure 17 UPFLOW FILTER CLIP BRACKET INSTALLATION 1 Determine the location to be used The furnace cabinet has dimples for location of the alter nate furnace clips Side retur...

Page 14: ...4 or the CAN CGA B149 Installation Codes and these instructions Determine that there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe condition 3 As f...

Page 15: ...isions of ANSI Z21 47 and CAN CGA 2 3 standards Category I furnaces operate with a non positive vent static pressure and with a flue loss of not less than 17 percent NOTE If desired a side wall termin...

Page 16: ...ATIONS d ELECTRICAL CONNECTIONS WARNING The cabinet must have an uninterrupted or unbroken ground according to National Electrical Code ANSI NFPA 70 latest edition and Canadian Electrical Code CSA C22...

Page 17: ...SING A 1 STAGE HEATING THERMOSTAT NO COOLING From Dwg 21B341437 P01 OUTDOOR UNIT NO TRANSFORMER SEE NOTE 6 From Dwg B341436 Rev 1 SEE NOTE 8 FURNACE TWIN SEE NOTE 7 B C B C TO 115 V 1 PH 60 HZ POWER S...

Page 18: ...PERATION OF UNIT NO 2 IS SYNCRONIZED WITH UNIT NO 1 VIA SIGNALS FROM TWIN CONNECTION SEE NOTE 4 SEE NOTE 3 ISOLATION RELAY FIELD SUPPLIED SEE NOTE 4 ISOLATION RELAY SEE NOTE 4 B C B C B C From Dwg 21B...

Page 19: ...g by closing its individual manual shut off valve dur ing any pressure testing of the gas supply piping sys tem at test pressures equal to or less than 1 2 psig CAUTION Use a backup wrench on the gas...

Page 20: ...from the utility company and compare to the nameplate rating This must not exceed the nameplate rating Gas Valve Adjustment Changes can be made by adjusting the manifold pres sure See Table 12 or cha...

Page 21: ...the heating value obtained from the local utility supplier for the gas being delivered at the in stalled altitude Input rate changes can be made by adjusting the manifold pressure min 3 0 max 3 7 in...

Page 22: ...is satisfied TO SHUT OFF For complete shutdown Move the control switch on the main gas valve to the OFF position See Figures 25 and 26 Disconnect the electrical supply to the unit CAUTION If this is d...

Page 23: ...CONTROL AND SAFETY SWITCH ADJUSTMENT LIMIT SWITCH CHECK OUT The limit switch is a safety device designed to close the gas valve should the furnace become overheated Since proper operation of this swit...

Page 24: ...g cycle the pressure switch will cause the gas valve to close and shut the unit down Carbon monoxide fire or smoke can cause serious bodi ly injury death and or property damage A variety of potential...

Reviews: