*UHM AIRFLOW - HEATING
0.1
0.3
0.5
0.7
0.9
CFM
592
617
623
617
606
Temp. Rise
61
59
58
59
60
Watts
78
109
141
173
233
CFM
626
651
655
649
639
Temp. Rise
58
56
55
56
57
Watts
79
110
142
175
236
CFM
660
684
688
682
671
Temp. Rise
55
53
53
53
54
Watts
81
111
144
177
241
CFM
732
755
757
751
739
Temp. Rise
50
48
48
48
49
Watts
87
115
149
185
254
CFM
1048
1065
1060
1052
1038
Temp. Rise
60
59
59
60
61
Watts
149
169
208
252
358
CFM
1107
1123
1116
1108
1094
Temp. Rise
57
56
56
57
58
Watts
167
186
226
271
386
CFM
1165
1181
1173
1165
1150
Temp. Rise
54
53
54
54
55
Watts
187
204
245
292
417
CFM
1291
1304
1293
1284
1269
Temp. Rise
49
48
49
49
50
Watts
236
250
293
343
490
CFM
1466
1476
1461
1451
1435
Temp. Rise
60
59
60
60
61
Watts
319
330
374
430
613
CFM
1548
1556
1540
1529
1512
Temp. Rise
57
56
57
57
58
Watts
364
373
419
476
679
CFM
1629
1637
1618
1608
1590
Temp. Rise
54
54
54
54
55
Watts
413
419
467
527
750
CFM
1803
1807
1785
1774
1755
Temp. Rise
49
48
49
49
50
Watts
529
532
582
646
864
100%
(high)
Heat
Low
1460
Medium Low
1540
Medium**
1620
High
1790
606
Medium**
1166
High
1289
672
High
743
639
Medium**
65%
(medium)
Heat
Low
1051
Medium Low
1109
40% (low)
Heat
Low
Heating
*UHMC100ACV4VA^
Furnace Heating Airflow (CFM) and Power (Watts) vs. External Static Pressure With Filter
Airflow
Setting
Target Airflow
(See Note 5)
External Static Pressure
Medium Low
0.1
0.3
0.5
0.7
0.9
CFM
728
758
785
805
819
Temp. Rise
62
59
57
56
55
Watts
119
107
102
94
108
CFM
769
797
822
840
853
Temp. Rise
58
56
54
53
53
Watts
113
107
111
113
133
CFM
813
841
864
880
890
Temp. Rise
55
53
52
51
50
Watts
108
107
122
135
160
CFM
863
889
910
923
930
Temp. Rise
52
50
49
49
48
Watts
104
108
135
160
191
CFM
1213
1232
1237
1232
1220
Temp. Rise
60
60
59
60
60
Watts
131
160
253
345
405
CFM
1279
1297
1299
1290
1274
Temp. Rise
57
57
56
57
58
Watts
147
178
281
382
445
CFM
1353
1369
1367
1355
1335
Temp. Rise
54
54
54
54
55
Watts
168
201
313
423
489
CFM
1434
1448
1443
1426
1402
Temp. Rise
51
51
51
51
52
Watts
197
229
352
469
538
CFM
1699
1707
1690
1659
1621
Temp. Rise
60
60
60
61
63
Watts
325
349
495
628
698
CFM
1790
1797
1775
1740
1696
Temp. Rise
57
57
57
59
60
Watts
382
400
551
685
752
CFM
1892
1896
1870
1830
1781
Temp. Rise
54
54
54
56
57
Watts
453
462
616
750
813
CFM
2004
2006
1975
1929
1873
Temp. Rise
51
51
52
53
54
Watts
540
538
694
822
880
100%
(high)
Heat
Low
1700
Medium Low
1790
Medium**
1890
High
2000
748
Medium**
1361
High
1440
832
High
880
788
Medium**
65%
(medium)
Heat
Low
1224
Medium Low
1289
45% (low)
Heat
Low
Heating
*UHMD120ACV5VA^
Furnace Heating Airflow (CFM) and Power (Watts) vs. External Static Pressure With Filter
Airflow
Setting
Target Airflow
(See Note 5)
External Static Pressure
Medium Low
Notes:
1. * First letter may be "A" or "T".
3. ** Factory setting.
2. ^ Letter may be “A” through “Z”.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
6. Target airflow is field selectable for high (100%) heat. Target airflow for low and medium
heat are percentages of high heat and are not field selectable.
Summary of Contents for ADHMB060BCV3VA
Page 37: ...UHM DHM SF 1H 37 Service Facts...
Page 39: ...UHM DHM SF 1H 39 Service Facts...
Page 41: ...UHM DHM SF 1H 41 Service Facts...
Page 47: ...UHM DHM SF 1H 47 Service Facts...
Page 49: ...UHM DHM SF 1H 49 Service Facts...
Page 51: ...UHM DHM SF 1H 51 Service Facts...