6
UHM-DHM-SF-1H
Service Facts
USER INTERFACE MENU
Power Up
== WAIT ==
A/TCONT900 Variable Speed
Standy Screen
System Status
Setup Options
[ ] = Current Setting
MODEL NUMBER
CMFRT CNT MODE
SERIAL NUMBER
COMM [COMM] 24VAC
* Unit specific
COOLING CFM
2
COOLING CFM
A/TUHMB060
3T [3T] 1.5T 2T 2.5T
*
A/TUHMB080
3T [3T] 3.5T 2T 2.5T
A/TUHMC100
4T [4T] 2.5T 3T 3.5T
CFM PER TON
CFM PER TON
A/TUHMD120
5T [5T] 3.5T 4T
400 [ 400 ] 430 450 290 310 330 350 370
A/TDHMB060
3T [3T] 1.5T 2T 2.5T
A/TDHMB080
3T [3T] 3.5T 2T 2.5T
HEAT CFM
HEAT CFM
A/TDHMC100
4T [4T] 2.5T 3T 3.5T
**
A/TDHMD120
5T [5T] 3.5T 4T
HT OFF DELAY
HEAT OFF DLY
** Unit specific
100s [100s] 140s 180s 60s
A/TUHMB060
960 [960] 1080 830 900
A/TUHMB080
1400 [1400] 1610 1120 1260
FACTORY DEFLTS
FACTORY DEFLTS
A/TUHMC100
1620 [1620] 1790 1460 1540
NO [NO] YES
A/TUHMD120
1890 [1890] 2000 1700 1790
A/TDHMB060
1040 [1040] 1160 900 950
EXIT
EXIT
A/TDHMB080
1400 [1400] 1610 1300 1350
NO [NO] YES
A/TDHMC100
1650 [1650] 1700 1500 1600
A/TDHMD120
1850 [1850] 2040 1660 1760
Information Menu
Information Options
MODEL NUMBER
MODEL
A/TUHM####
SERIAL NUMBER
SERIAL
#####
SW REV NUMBER
SW REV NUMBER
#####
SYSTEM STATUS
SYSTEM STATUS
OFF
REQUESTED CFM
REQUESTED CFM
0 CFM
LAST 4 FAULTS
LAST 4 FAULTS
NO ALERTS
INDOOR ALERTS
INDOOR ALERTS
NO ALERTS
UNIT TEST
UNIT TEST
UNIT TEST
UNIT TEST
SIMPLE
GAS VAL SETUP
TEMP SENSOR
TEMP SENSOR
SNSR1 [SNSR1] SNSR2 DLT2-1
UNIT TEST SIMPLE
GAS VAL SETUP
MOTOR RPM
MOTOR RPM
NO [NO] YES
MIN [MIN] MAX
0 RPM
INDUCER RPM
INDUCER RPM
0 RPM
ARE YOU SURE
ARE YOU SURE
NO [NO] YES
NO [NO] YES
RESET LST FAULT
RESET LST FAULT
NO [NO] YES
PART LIST
PART LIST
CNT*****
PM SERIAL NUM
PM SERIAL NUM
#####
CNTNGNCY MODE
CNTNGNCY MODE
OR
CNTNGNCY MODE
1
NOT AVAILABLE (with data line connected and active)
NO [YES] YES (no data line connected)
EXIT
EXIT
NO [NO] YES
CNTNGNCY MODE <STAGE>
CNTNGNCY MODE <STAGE>
STAGE [OFF] OFF 1 2
DUTY CYCLE [10] 10 20 30 40 50
START [NO] NO YES
NOTES:
EXIT [NO] NO YES
1
This menu will only display at comfort control mode when A/TCONT900 is NOT connected
ARE YOU SURE [NO] NO YES
ENTER
2
Shown only when Communicating Outdoor Unit is not detected
ENTER
ENTER
ENTER
Summary of Contents for ADHMB060BCV3VA
Page 37: ...UHM DHM SF 1H 37 Service Facts...
Page 39: ...UHM DHM SF 1H 39 Service Facts...
Page 41: ...UHM DHM SF 1H 41 Service Facts...
Page 47: ...UHM DHM SF 1H 47 Service Facts...
Page 49: ...UHM DHM SF 1H 49 Service Facts...
Page 51: ...UHM DHM SF 1H 51 Service Facts...