background image

34

18-CD25D1-2

Installer’s Guide

6.

To increase outlet pressure, turn the regu
lator adjust screw clockwise. To decrease
outlet pressure, turn the regulator adjust
screw counter-clockwise. The final Manifold
Pressure setting shall be as specified in
Table 9 with an input of no more than
nameplate rating and no less than 93% of
the nameplate rating, unless the unit is de-
rated for high altitude.

7.

Replace high adjustment regulator cover
screw and tighten securely.

8.

Cycle the Valve several times to verify
regulator setting.

g.

Turn off all electrical power to the system.

h. Remove the Manometer and flexible tubing.

Remove the barbed fitting and replace the plug
or tighten the pressure test screw.

i.

Turn on electrical power to the system and en-
ergize valve.

j.

Using a leak detection solution or soap suds,
check for leaks at plug or pressure boss screw.

NOTE: The Manifold Pressure must be referenced to
the Burner Box. The Burner Box pressure tap equalizes
the Gas Valve pressure regulator. Manifold Pressure is
checked by installing a tee (field supplied) in the tub-
ing, between the tee coming from the Burner Box tube
and the Gas Valve, in addition to the regular Gas Valve
pressure tap on the outlet side of the Gas Valve. See
Figure 32.

Table 7 lists the main burner orifices used with the Fur-
nace. If a change of orifices is required to correct the
Furnace input rating refer to Table 10.

REINSTALLATION OF THE BURNER BOX COVER

Figure 34 shows the correct way to reinstall the Burner
Box cover if adjustment or replacement of the flame
sensor, hot surface igniter, or main burner orifices have
required removal of the cover.

HIGH ALTITUDE DERATE

Input ratings (BTUH) of these Furnaces are based on
sea level operation and should not be changed at eleva-
tions up to 2,000 ft.
If the installation is 2,000 ft. or above, the Furnace input
rate (BTUH) shall be reduced 4% for each 1,000 ft. above
sea level.
Installation of this furnace at altitudes above 2,000 ft.
(610m) shall be in accordance with local codes, or in the
absence of local codes, the 

National Fuel Gas Code,

ANSI Z223.1/ NFPA 54

 or 

National Standard of

Canada, Natural Gas and Propane Installation Code,
CSA B149.1

. Installation of this furnace at altitudes

above 2,000 ft. (610m) shall be made in accordance with
the listed high Altitude Conversion Kit available with
this furnace.

The Furnace input rate shall be checked by clocking the
gas flow rate (CFH) and multiplying by the heating
value obtained from the local utility supplier for the gas
being delivered at the installed altitude. Input rate
changes can be made by adjusting the Manifold Pres-
sure (min 3.0 - max 3.7 in. W.C. - Natural Gas) or
changing orifices (orifice change may not always be re-
quired).
If the desired input rate can not be achieved with a
change in Manifold Pressure, then the orifices must be
changed. LP installations will require an orifice change.

IMPORTANT:

Reinstall the propane orifices to the same depth as the ori-
fices supplied with the equipment.

TABLE 8

TABLE 9

GAS FLOW IN CUBIC FEET PER HOUR

2 CUBIC FOOT DIAL

SEC. FLOW

SEC. FLOW

SEC. FLOW

SEC. FLOW

8

900

29

248

50

144

82

88

9

800

30

240

51

141

84

86

10

720

31

232

52

138

86

84

11

655

32

225

53

136

88

82

12

600

33

218

54

133

90

80

13

555

34

212

55

131

92

78

14

514

35

206

56

129

94

76

15

480

36

200

57

126

96

75

16

450

37

195

58

124

98

73

17

424

38

189

59

122

100

72

18

400

39

185

60

120

104

69

19

379

40

180

62

116

108

67

20

360

41

176

64

112

112

64

21

343

42

172

66

109

116

62

22

327

43

167

68

106

120

60

23

313

44

164

70

103

124

58

24

300

45

160

72

100

128

56

25

288

46

157

74

97

132

54

26

277

47

153

76

95

136

53

27

267

48

150

78

92

140

51

28

257

49

147

80

90

144

50

FINAL MANIFOLD PRESSURE SETTINGS (inches w.c.)

FUEL

2nd Stage Max.

1st Stage Max.

NATURAL GAS

3.5" W.C.

1.7" W.C.

LP GAS

10.5" W.C.

6.0" W.C.

See Table 10 for help in selecting orifices if orifice change
is required. Furnace input rate and temperature rise
should be checked again after changing orifices to con-
firm the proper rate for the altitude.
The vent length table on page 14 shows the required
vent lengths for installations at various altitudes. An op-
tional high altitude kit is available for installations
above 5000 feet. Installations above 12,000 feet are not
allowed.

Summary of Contents for AUX2B060AFV3VA

Page 1: ...th or serious injury b CAUTION indicates a potentially hazardous situation which if not avoided may result in minor or mod erate injury It is also used to alert against unsafe practices and hazards in...

Page 2: ...em for proper size and hori zontal pitch as required in the National Fuel Gas Code ANSI Z223 1 NFPA 54 or the CSA B149 1 Natural Gas and Propane Installation Code and these instruction Determine that...

Page 3: ...also be handled by a duct s sealed to the Fur nace casing and terminating outside the space con taining the Furnace 8 A gas fired Furnace for installation in a residential garage must be installed as...

Page 4: ...ace is moved into place be sure to consider the following requirements 1 Is the location selected as near the chimney or vent and as centralized for heat distribution as practical 2 Do all clearances...

Page 5: ...CHARGER Charges the contaminants 2 COLLECTION CELL removes and collects very small impurities from the air 3 Power Supply the solid state power supply converts the 24 Volt AC to the high voltage dire...

Page 6: ...6 18 CD25D1 2 Installer s Guide UX2 UPFLOW HORIZONTAL OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES...

Page 7: ...the COLLECTION CELL and remove and dis card the cardboard over the cell NOTE No sheetmetal screws may be used from 0 4 from the bottom of the unit Screws will interfere with the Air Cleaner See Figure...

Page 8: ...rods with a substantial metal support frame that supports the entire length of the furnace The rods need to be of sufficient length to allow for proper clearances from combustible materials The frame...

Page 9: ...to Table 3 for minimum open areas required 2 All air from outdoors as in Figure 11 The confined space shall be provided with two permanent open ings one commencing within 12 inches of the top and one...

Page 10: ...space containing the Furnace Where there is no complete return duct system the return connection must be run full size from the Furnace to a location outside the utility room basement attic or crawl...

Page 11: ...can cause serious bodily injury death and or property damage A variety of potential sources of carbon monoxide can be found in a building or dwelling such as gas fired clothes dryers gas cooking stov...

Page 12: ...and fittings See Table 4 page 12 Where the system is routed to the outdoors through an existing masonry chimney containing flue products from another gas appliance or where required by local codes th...

Page 13: ...e structure a straight section of pipe long enough to exit the Furnace cabinet must be attached to the inlet air side with an elbow which is 5 to 10 equiv ft in stalled on the end to prevent dust and...

Page 14: ...d collar of the combustion air inlet should just be a friction fit It is recommended that the inlet air joint be sealed with RTV type sealant to al low the joint to be separated for possible future se...

Page 15: ...rger diameter but never smaller than the vent pipe 3 MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED THE LENGTH SHOWN IS NOT A COMBINED TOTAL IT IS THE MAXIMUM LENGTH OF EACH Vent or Inlet air pipes 4 One S...

Page 16: ...mm thick Armaflex type insulation or equal If the space is heated sufficiently to prevent freezing then the insulation would not be required If domestic water pipes are not protected from freezing th...

Page 17: ...it is recommended that a corrosion resistant shield 24 inches square be used behind the vent termi nal This shield can be wood plastic sheet metal etc Also silicone caulk all cracks seams and joints w...

Page 18: ...fasteners suited to the outside or inside wall surfaces NONCOMBUSTIBLE MATERIAL WALL The hole through the wall must be large enough to maintain pitch of vent and properly seal Use cement mortar seal...

Page 19: ...penetrating roof with a 2 PVC vent pipe a 2 electrical conduit flashing may be used for a weather tight seal Lubricate flexible seal on flashing before PVC pipe is pushed through the seal Field Suppli...

Page 20: ...NG 6 IN MIN SEE CAUTION STAINLESS STEEL VENT CAP STAINLESS STEEL VENT CAP OP TIONAL STAINLESS STEEL VENT CAP OP TIONAL CAUTION Do NOT run vent through chimney for wood burn ing or oil Furnaces or inci...

Page 21: ...m for appliances 10 000 Btuh 3 kw 12 inches 30 cm for appliances 10 000 Btuh 3 kw and 100 000 Btuh 30 kw 36 inches 91 cm for appliances 100 000 Btuh 30 kw 4 feet 1 2 m below or to side of opening 1 fo...

Page 22: ...83m 3 feet 91 cm above if within 10 feet 3m horizontally L Clearance above a paved sidewalk or paved driveway located on public property 7 feet 2 13 m M Clearance under veranda porch deck or balcony 1...

Page 23: ...detector with alarm and battery back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be met at the time of completion of installat...

Page 24: ...is needed in this line All horizontal applications are left side only and require repositioning the condensate canister trap to the exterior of the cabinet Additionally the drain tubing connected to t...

Page 25: ...ain may be cleaned or inspected by removal of the drain tube at the header Evaporator and Furnace condensate drain piping may be manifolded together as shown in Figure 29 A pri mary drain vent stack m...

Page 26: ...only for thermostats requiring connection to transformer common terminal 11 Optional humidistat is to be connected between R and BK Factory installed jumper R to BK on the circuit board must be cut i...

Page 27: ...delays 9 Optional humidistat is to be connected between R and BK Factory installed jumper R to BK on the circuit board must be cut if optional humidistat is used The jumper must also be cut when apply...

Page 28: ...R SEE NOTE 9 FIELD ADDED JUMPER W1 TO W2 2ND STAGE WILL FIRE 10 MINUTES AFTER 1ST B C B C TO 115 V 1 PH 60 HZ POWER SUPPLY PER LOCAL CODES HUM SEE NOTE 5 FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAG...

Page 29: ...NOTE 9 W14 JUMPER SEE NOTE 9 From Dwg B342020 Rev 0 B C B C TO 115 V 1 PH 60 HZ POWER SUPPLY PER LOCAL CODES HUM SEE NOTE 5 FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE 2 STAGE HEATING 1 ST...

Page 30: ...oling only non heat pump systems jumper Y to O for proper operation of the delay profiles and the Humidistat For two compressor or two speed systems jumper Ylo to O W14 OUTDOOR UNIT NO 2 NO TRANSFORME...

Page 31: ...lled ahead of the controls as shown in Figures 31 32 The Furnace and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at...

Page 32: ...ITH MANUAL SHUTOFF MAIN MANUAL SHUTOFF VALVE GROUND UNION JOINT DRIP LEG Figure 30 MAIN MANUAL SHUTOFF VALVE GROUND UNION JOINT AUTOMATIC GAS VALVE WITH MANUAL SHUTOFF MAIN MANUAL SHUTOFF VALVE GROUND...

Page 33: ...To adjust the Manifold Pressure a Turn off all electrical power to the system b Attach a Manifold Pressure gauge to the outlet pressure tap marked OUT PRESS TAP on White Rodgers gas valve model 36G se...

Page 34: ...ence of local codes the National Fuel Gas Code ANSI Z223 1 NFPA 54 or National Standard of Canada Natural Gas and Propane Installation Code CSA B149 1 Installation of this furnace at altitudes above 2...

Page 35: ...59 60 55 56 57 60 61 55 56 57 60 62 55 56 58 61 62 56 56 59 62 63 56 56 59 63 63 56 57 60 63 64 From National Fuel Gas Code Table F 4 TABLE 10 Turn the main Gas Valve toggle switch See Figures 30 31...

Page 36: ...irements are satisfied The induced draft blower is reduced to low speed allow ing the 2nd Stage Pressure Switch contacts to open and the Gas Valve is reduced to 1st Stage The indoor blower motor is re...

Page 37: ...tches 5 and 6 The following table and graph explain the delay off set tings AIRFLOW ADJUSTMENT WARNING Disconnect power to the unit before removing the blower door Allow a minimum of 15 seconds for IF...

Page 38: ...GAS SUPPLY FAILURE If loss of flame occurs during a heating cycle the system Integrated Control Module will recycle the ig nition sequence then if ignition is not achieved the Integrated Control Modul...

Page 39: ...se Lay the FIELD CHARGER on a secured flat surface 8 Wipe down the face Plate of the FIELD CHARGER with a dry shop towel or use a vacuum cleaner Do not disassemble the FIELD CHARGER WHOLE HOUSE AIR CL...

Page 40: ...und inside the Furnace casing Also turn off electrical power to the Furnace and contact the service agency designated by your dealer WARNING Should overheating occur or the gas supply fail to shut off...

Page 41: ...ng complies with State of California law Proposition 65 This product contains fiberglass wool insulation Fiberglass dust and ceramic fibers are believed by the State of California to cause cancer thro...

Page 42: ...80 1 1 4 1050 730 590 520 440 400 370 This table is based on pressure drop of 0 3 inch W C and 0 6 SP GR gas Fault Code Reset The last 4 Fault Codes can be erased from memory by powering up the contro...

Page 43: ...ameplate 8 Energize the system and carefully observe its operation make any necessary adjustment 9 Adjust ozone setting if needed 10 Instruct owner on proper operating procedure and leave Use and Care...

Page 44: ...improvement it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 For more information contact your local dealer distributor Literature Orde...

Reviews: